- 48 -
Circuit diagrams are shown in figure 1 or 2.
The UPS must be installed with flexible conduit, except for M-UPS015AE2S.
For pluggable devices, outlets should be located close to the UPS and easily accessible.
For M-UPS015AE2S-U
For permanently connected UPS, an easily accessible disconnect device shall be incorporated
into the building installation wiring.
Except for M-UPS015AE2S-U
Table 1. Input rating, wire size, torque, external input circuit breaker size
INPUT & GROUND
2POLE CIRCUIT
BREAKER
MODEL
Vin(V) Iin(A)
WIRE
SIZE
AWG
Type of
Closed-loop
Terminal
TIGHTENING
TORQUE
(N
・
m)
V
A
M-UPS015AE2R-Ux
7.5
14
R2-4
2.0
10
M-UPS030AE2B-Ux-y
M-UPS030AE2R-Ux-y
M-UPS030AE2C-Ux-y
200/208
220/230
240
15
10
R5.5-4
2.0
AC240
20
x: Any letters
y: Any letters
Table 2. Output rating, wire size, torque, external output circuit breaker size
OUTPUT
2POLE CIRCUIT
BREAKER
MODEL
Vo(V)
Io(A)
WIRE
SIZE
AWG
Type of
Closed-loop
Terminal
TIGHTENING
TORQUE
(N
・
m)
V
A
M-UPS015AE2R-Ux
7.5/7.2
6.8/6.5
6.3
14
R2-4
2.0
10
M-UPS030AE2B-Ux-y
M-UPS030AE2R-Ux-y
M-UPS030AE2C-Ux-y
200/208
220/230
240
15/14.4
13.6/13
12.5
10
R5.5-4
2.0
AC240
20
7.2 Additional Description for UL Type
x: Any letters
y: Any letters