5.1  Inspection 

- 26 -

Daily 

maintenance

1.

Cleaning

Remove any dust from the UPS ventilation and cooling fan with a vacuum

cleaner. Wipe the surface of the UPS with a soft, dry cloth.

2.

Abnormality

Contact the distributor or maintenance company where you purchased the

UPS if you observe;

Abnormally heated surface of the UPS, wires, and outlets

Loud noises

Unusual smell

Summary of Contents for GX200 Series

Page 1: ...Fuji Electric Co Ltd USER S MANUAL Uninterruptible Power Supply GX200 Series 1 5kVA 3kVA Model M UPS015AE2S M UPS015AE2R M UPS030AE2B M UPS030AE2R M UPS030AE2C INR HG5980...

Page 2: ...a use If using this product for such a use consult with our sales representatives Prevention of radio interference Important This product is class A information technology device based on the standar...

Page 3: ...The condition of the UPS LED Indications Lit Flashing Out Caution Following warning signs are included to prevent the user from damaging the UPS and the connected devices product is not used properly...

Page 4: ...ound terminal class D grounding Commercial power supplies usually have electrodes on the grounded and ungrounded sides in addition to the grounding electrode earth Check before connecting Connecting i...

Page 5: ...eavy Caution in handling the UPS Take out the UPS in a level and flat place The weight of the UPS is as follows M UPS015AE2S 24 kg 12 kg without batteries M UPS015AE2R 26 kg 14 kg without batteries M...

Page 6: ...ouble When performing a rolling blackout or when unplugging the AC input plug from the input power outlet or when turning off the input breaker on the rear of the UPS make sure that the RUN LED green...

Page 7: ...harge the battery by operating the UPS for 12 hours or more every two months After charging the battery perform the battery check If the UPS is not used for a long period of time the battery may becom...

Page 8: ...voltage to the UPS is directly output as output voltage If a voltage exceeding the input voltage range of the connected equipment is applied the connected equipment may be damaged Avoid single wire g...

Page 9: ...able Preparation before connection Connecting the output cable Connecting the input cable 3 3 Interface port 16 CN1 standard monitoring interface CN2 PC interface Setting up the Output Voltage 18 3 4...

Page 10: ...Battery 33 Timing of battery replacement Method of battery replacement Disposal and storage of battery 5 5 Replacing the Cooling Fan 36 Timing of cooling fan replacement Method of cooling fan replacem...

Page 11: ...UPS015AE2R User s manual Warranty Rack mount rails for right side and left side Screws for rack mount rail fastening Washers for rack mount rail fixing 1 copy 1 set 10 set 8 set M UPS030AE2B User s ma...

Page 12: ...2 1 Name and Main Function of Each Part M UPS015AE2S M UPS015AE2R M UPS030AE2R RUN ALARM OVERLOAD BYPASS COND BATTER I Y TION RESET BATT C H E C K RUN ALARM OVERLOAD BYPASS COND BATTER I Y TION RESET...

Page 13: ...2 1 Name and Main Function of Each Part 3 M UPS030AE2B M UPS030AE2C RUN ALARM OVERLOAD BYPASS COND BATTER I Y TION RESET BATT C H E C K...

Page 14: ...ously for 3 seconds Press the switches again simultaneously for 3 seconds to return the UPS to normal operation Vent hole Allows ventilation inside the UPS The air direction is intake Cooling fan Cool...

Page 15: ...flowing Output to connected device AC AC converter Step up chopper Bypass UPS Charger Batteries Occurrence of input power supply error Electricity is flowing Electricity is not flowing Output to conn...

Page 16: ...ctricity flow during automatic bypass operation Manual bypass operation Manual bypass operation can be switched to bypass operation during normal operation Press the RESET and BYPASS switches simultan...

Page 17: ...or near residential areas This UPS is a Class A information technology device according to VCCI Voluntary Control Council for Interference by Information Technology Equipment standards Use of this UPS...

Page 18: ...d environment Temperature 15 to 25 C Humidity 30 to 70 No condensation Front Rear UPS 10 cm Intake Exhaust Front UPS Rear Space for maintenance of cooling fan batteries Space for maintenance of coolin...

Page 19: ...prevent an accident such as an overturn or a drop The mass of the UPS refers to Caution about Safety M UPS015AE2S and M UPS030AE2B M UPS030AE2B For preventing an overturn of the UPS the UPS fixes to a...

Page 20: ...type brackets to a floor with an anchor bolt Please prepare the anchor bolts by user M UPS015AE2R M UPS030AE2R 1 Loosen the screw of the right rail for rack mounting and the left rail for rack mountin...

Page 21: ...mounting in the place of the corner hole with the washers Set up the bending part in the rail to the lower side and inside The washers might become unnecessary by the kind of the rack 3 Put the syste...

Page 22: ...ak or more is applied the filter circuit in the input section may be damaged The input voltage range of the UPS is from 160VAC to 288VAC tolerance If the input voltage is different from the above prov...

Page 23: ...ncy variation within 5 of rated frequency less than 1Hz per second Voltage waveform distortion within 5 Voltage zero cross condition No multiple zero cross 1 Check the input power supply The input pow...

Page 24: ...nnection Form L R AC input ungrounded side terminal N S AC input Grounded side terminal GND FG Ground l U AC output ungrounded side terminal Input output terminal block n V AC output grounded side ter...

Page 25: ...he AC output cable to the AC output terminal block Have the ground terminal securely grounded Connecting the input cable 1 In the case of M UPS015AE2S plug the AC input on the back of the UPS to an in...

Page 26: ...it is time for battery replacement 2 5 Opens on action 2 7 Closes on action Input power supply error signal No voltage contact signal due to a voltage error in the power supply If the power failure l...

Page 27: ...econds 6 7 Serial data input RX 9 7 Serial data output TX 7 RS 232C serial signal See Note 3 Signal ground SG Communication method Baud rate 2400 bps 8 bits 1 bit Data length Stop bit Parity non Chara...

Page 28: ...2 Press the RUN STOP switch on the front of the UPS for 1 second The buzzer will sound if the switch is received 3 An output stops The RUN LED green on the front of the UPS blinks slowly in the cycle...

Page 29: ...t breaker on the back of the UPS The RUN LED green on the front of the UPS blinks slowly in the cycles of 1 6 sec 8 Press the RUN STOP switch on the front of the UPS for 1 second A buzzer sounds when...

Page 30: ...on the front of the UPS will flash slowly in the cycles of 1 6 sec Refer to Chapter 3 2 Connecting the Cables Damage Check the voltage set by the voltage setting switch is within the input voltage ra...

Page 31: ...lock The RUN LED green on the front of the UPS lights up The BATTERY CONDITION LED green on the front of the UPS indicates the battery charge level by the lighting type Press the RUN STOP switch for 1...

Page 32: ...onds After that if the battery is normal the BATTERY CONDITION LED green on the front of the UPS will again indicate the battery charge level and the UPS will return to the normal operation If normal...

Page 33: ...green is blinking slowly 1 6 second cycle Do not unplug the AC input plug from the power outlet or turn off the input breaker on the back of the UPS without turning off the UPS Otherwise it will caus...

Page 34: ...he UPS flashes slowly cycles of 1 6 seconds If the output fails to stop normally See Chapter 6 Troubleshooting 4 Turn off the input breaker on the distribution board 4 2 Turning off the UPS RUN ALARM...

Page 35: ...off the input power and disconnect the connection to the AC input terminals R S Only authorized maintenance personnel should perform maintenance other than daily inspections such as replacing batterie...

Page 36: ...ilation and cooling fan with a vacuum cleaner Wipe the surface of the UPS with a soft dry cloth 2 Abnormality Contact the distributor or maintenance company where you purchased the UPS if you observe...

Page 37: ...power outage Turn off the connection device and the UPS before performing the planned power outage 1 Turn off the power to the connected device 2 Press the RUN STOP switch on the front of the UPS for...

Page 38: ...nd cycle 2 Press the RUN STOP switch on the front of the UPS for 1 second When the power is on a warning beep will sound 3 AC voltage is output from the AC outlet or the output terminal block and the...

Page 39: ...due to a battery malfunction When performing a battery check other than the automatic check IMPORTANT Do not perform the battery checks continuously When performing battery checks the internal battery...

Page 40: ...s the buzzer will sound again to complete the battery check Press the BATT CHECK switch for 2 seconds Buzzer will sound RUN ALARM OVERLOAD R BYPASS COND BATTE I Y TION RESET BATT C H E C K RUN ALARM O...

Page 41: ...the normal operation If the battery is not fully charged A warning beep will sound and the BATTERY CONDITION LED orange on the front of the UPS will flash Go to step 4 RUN LED green is lit BATTERY CON...

Page 42: ...will turn off and the battery charge level indicator green will display 5 Return to step 2 and perform the battery check manually If the UPS enters the battery not fully charged condition again it is...

Page 43: ...When the backup time of the battery has been lowered to 3 minutes or less at the rated load Battery life is greatly affected by ambient temperature and connected device conditions if the UPS is used...

Page 44: ...or details contact the distributor or maintenance company from whom you purchased the UPS Note The UPS performs a bypass operation when hot swapped In the bypass operation state battery operation cann...

Page 45: ...ion when disposing of or storing batteries When disposing of used batteries apply insulation tape to the battery terminals to prevent short circuits and dispose of them separately from dry cell batter...

Page 46: ...fan life may cause the internal temperature of the UPS to exceed its rating The cooling fan has reached the end of its service life in the following case At the second battery replacement Cooling fan...

Page 47: ...nance company from whom you purchased the UPS Note Replace the cooling fan in a short period of time during live operation This product is in bypass operation when the cooling fan is replaced during l...

Page 48: ...OFF the power for the UPS and turn off the input breaker on the back of the UPS See 4 2 Power OFF for details 3 Place the UPS in the original box and store it UPS stored longer than two months IMPORT...

Page 49: ...ot stop follow these steps refer to Chapter 4 2 Turning Off the UPS 1 Turn off the connected device 2 Press the ON OFF switch on the front of the UPS for 1 second 3 The output stops The RUN LED green...

Page 50: ...n Mode List LED Flashing Type Symbol Flash pattern a Fast flashing 0 4 second period b Slow flashing 1 6 second period Warning Sound Type Symbol Warning sound i Beep beep beep beep ii Beep beep stops...

Page 51: ...3 Device is not in 3 and input breaker is tripped reset it No 3 status contact your distributor or maintenance company Input power failure continues and the machine is stopped because the battery has...

Page 52: ...voltage In case this state lasts for 100 seconds the UPS will stop operating due to Output Overload No 12 Unable to operate battery mode when input power failure occurs Output short circuit will stop...

Page 53: ...ALARM orange OVER LOAD orange BYPASS orange BATTERY CAPACITY green orange 14 Lit Charged amount 1 Battery voltage drop due to continuing the battery operation Battery Check Error The battery may not b...

Page 54: ...automatic battery check 18 b Slow flashing a Fast flashing 1 Setting error of rated output voltage Setting Error of the Rated Output Voltage Wrong setting of the output voltage at the rear of the UPS...

Page 55: ...rance 160 288V Frequency 50 Hz or 60 Hz 5 Number of phase Single phase 2 wire with a ground terminal Capacity 1500 VA or less Grounding system Single line grounding Power factor 0 97 or more at the ra...

Page 56: ...or 60 Hz 5 Number of phases Single phase 2 wire with a ground terminal Capacity 3000 VA or less Grounding method Single line grounding Power factor 0 97 or more at the rated operation AC input Input h...

Page 57: ...PS must be secured to the floor with the provided brackets For all models without M UPS015AE2S need to provide external disconnect and over current protection devices for AC input and AC output A prop...

Page 58: ...REAKER MODEL Vin V Iin A WIRE SIZE AWG Type of Closed loop Terminal TIGHTENING TORQUE N m V A M UPS015AE2R Ux 7 5 14 R2 4 2 0 10 M UPS030AE2B Ux y M UPS030AE2R Ux y M UPS030AE2C Ux y 200 208 220 230 2...

Page 59: ...rminal Block M UPS015AE2R L R N S PE G S1 FG AC OUTLET PLUG M UPS015AE2S AC I O Terminal Block M UPS015AE2R Fig 2 M UPS030AE2 circuit diagram Dual Conveter Boost Chopper l U n V AC I O Terminal Block...

Page 60: ...ng batteries use only those specified by the company Risk of electric shock Battery and cooling fan servicing should be performed by technically qualified service personnel The UPS has an internal ene...

Page 61: ...oots d Do not place tools or metal parts on the battery e Disconnect the charging source before connecting or disconnecting the battery terminals f If the battery is inadvertently grounded remove the...

Reviews: