- 47 -
7.2
Additional Description for UL Type
IMPORTANT SAFETY INSTRUCTIONS
These important instructions relate to the installation and maintenance of the
UPS GX200 series.
Internal battery voltage is xx Vdc, where xx stands as follows.
Models M-UPS015AE2S-U with suffix: xx is 48Vdc
Models M-UPS015AE2R-U with suffix: xx is 48Vdc
Models M-UPS030AE2B-U with suffix: xx is 96Vdc
Models M-UPS030AE2R-U with suffix: xx is 96Vdc
Models M-UPS030AE2C-U with suffix: xx is 96Vdc
This unit intended for installation in a controlled environment and maximum
ambient temperature is 25
℃
(temperature controlled, indoor area free of
conductive contaminants).
If ambient temperature is higher than 25
℃
, the output current decrease as
follows.
Ambient
Output rating
100%
90%
to 25
℃
to 35
℃
to 40
℃
80%
This UPS must be secured to the floor with the provided brackets.
For all models without M-UPS015AE2S, need to provide external
disconnect and over current protection devices for AC input and AC
output. A properly rated UL listed branch circuit breaker can provide both
functions.
Since the input side of the UPS is not equipped with a circuit breaker (UL
listed circuit breaker for backflow protection), this circuit breaker must be
used when shipped. All models not using the M-UPS015AE2S must have
a circuit breaker connected for use with the UPS. The trip current ratings of
the circuit breakers (2-pole type) are listed in Table 1 and Table 2.
Wiring shall use UL and CSA approved closed loop terminal connectors
that are compatible with the wire size and fully insulated to the terminals.
Connectors shall be secured with a crimp tool specified by the connector
manufacturer
Use 75°C copper wire for conductors.
Wire sizes and tightening torques are shown in Tables 1 and Table 2.