16
INP-TN512878-E
4.5 Method to convert analog signal to integration pulse
Method to output as pulses the value of flow rate 0 to 50 T/H (0 to 100%) under the weight of one
pulse/1T.
Figure 4-11
A value of flow rate 0 to 50t/H is integrated with analog integration wafer (8C), and when 1t(that is,
1t/50t = 2%) is reached, the pulse of 1 pulse weight time (40 seconds) is ON by the comparison wafer
(08) in this example. While said pulse is ON, the flow rate for one pulse (1T = 90t/H
×
40 seconds)
is subtracted from the analog integration wafer (8C) by way of the subtraction wafer (63).
The values of constant CON6 (90t/H=180%) and CON9 (40 seconds) are determined arbitrarily so
that their product becomes one-pulse weight, that is, 1t. If the output pulse width, 40 seconds is too
long, the one-shot circuit is located after the pulse generation wafer (88). An arbitrary pulse width
can be created as a result.