INP-TN512878-E
15
4.4 How to use dead time wafer
4.4.1 Series connection of dead time wafers
There are three dead time wafers. Two dead time wafers (dead time wafers 1 and 2) of up to 120
seconds (2 minutes) in one-second interval and one dead time wafer (dead time wafer 3) of up to 60
minutes in 30-second interval. In case it is necessary to create dead time of up to 3 minutes by
series connection of two dead time wafers, it is done as shown below.
Figure 4-10
Note: With a dead time wafer, even if setting of dead time L exceeds the setting range, i.e., 2
minutes, it is limited to 2 minutes internally. Furthermore, even if the dead time is set a
minus value, it is limited to 0 minute.
The above example shows a case to produce a dead time of 3 minutes using dead time wafers (1) and
(2). When dead time L of dead time wafer (1) is set at 180 seconds, it is limited to 120 seconds,
and when dead time L of dead time wafer (2) is set at 120 seconds, it is limited to 60 seconds by
wafer 63, and dead time of 3 minutes is produced as a result.