All Power-Limited Wiring
Municipal Circuit -
Local Energy
Master Box/Releasing
Application, Route
under PCB.
Non Power-Limited.
DACT wiring.
Non Power-Limited
Battery wiring. Non Power-Limited
120/240 VAC wiring.
Non Power-Limited
Municipal Circuit
Reverse Polarity
Application. Power-
Limited
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25" away from any non power-limited wiring. All power-limited and non power-
limited wiring must enter and exit the cabinet through different knockouts and/or conduits.
Figure 4 Power Limited/Non-power Limited Wiring
Knockouts for Non Power-Limited wiring.
This includes 120/240 VAC, Batteries (if
remote from enclosure, DACT (optional)
and Municipal (optional) Wiring.
9000-0447
43 of 43