147
Item
Default Setting
Remark
Signal Level
Ethernet
Internet Protocol
192.168.0.1
Port
44818
Communication Method EtherNet/IP
2.7.2.2
PLC Resource Review
Device Description
Data bit Input
format
Min.
Max.
O
Output File
1/16
O F:S.D
O0:0.0
O0:30.255
I
Intput File
1/16
I F:S.D
I1:0.0
I1:30.255
S
Status File
1/16
S F:E
S2:0
S2:163
B
Bit File
1/16
B F:E
B3:0
B255:255
T
Timer File
1/16
T F:E.D
T4:0.0
T255:255.2
C
Counter File 1/16
C F:E.D
C5:0.0
C255:255.2
R
Control File
1/16
R F:E.D
R6:0.0
R255:255.2
N
Integer File
1/16
N F:E
N7:0
N255:255
F
Floating File 32
F F:E
F8:0
F255:255
A
ASCII File
1/16
A F:E
A9:0
A255:255
ST
String File
1/16
ST F:E.D
ST9:0.0
ST255:255.41
2.7.2.3
Connecting to HMI
The SLC series PLC can be configured using the same procedure as the Micrologix
series configuration. The figures refer to the Micrologix PLC but the procedure is the
same.
Configuring IP Address on PLC
If the IP address needs to be configured, follow the steps below.
Use the applications RSLinx Classic Lite and RSLogix 500 to configure the IP address of
the PLC.
First open RSLinx Classic Lite to set up a connection between the computer and PLC.
An Ethernet cable needs to be connected to the PLC and the computer must be online.
In the Communications menu tab, select Configure Drivers. Select EtherNet/IP Driver
and press ‘Add New’. Select “Your Network Interface Card” and press OK. Start the
Driver and close out of the dialog window.
Summary of Contents for P5 Series
Page 1: ...1 P5Series ...
Page 53: ...53 Note For more detailed information please refer to the PLC manual Connecting PLC to HMI ...
Page 93: ...93 Note For more detailed information please refer to the PLC manual HMI 設定 ...
Page 116: ...116 In the dialog window the IP address can be changed Press OK to confirm the setting ...
Page 124: ...124 Note For more detailed information please refer to the PLC manual Connecting PLC to HMI ...
Page 149: ...149 Note For more detailed information please refer to the PLC manual Connect PLC to HMI ...
Page 152: ...152 Note For more detailed information please refer to the PLC manual Connecting PLC to HMI ...
Page 158: ...158 Note For more detailed information please refer to the PLC manual Connect PLC to HMI ...
Page 161: ...161 Note For more detailed information please refer to the PLC manual Connecting PLC to HMI ...
Page 200: ...200 Note For more detailed information please refer to the PLC manual Connecting PLC to HMI ...
Page 220: ...220 2 choose model and build project click PLC on the top select connect to connect ...
Page 221: ...221 connect success as shown below HMI Setting ...