Fastus UR-DS4AD User Manual Download Page 32

32 

13.

 

Troubleshooting 

How to handle UR-DS4AD/UR-DS4DA when it does not work properly or when problems occur. 

Common for UR-DS4AD/UR-DS4DA 

Symptom 

Checkpoints and countermeasures 

POWER LED does not light up 

Check that voltage is applied to the Unit power’s 24 V and 0 V and the 
I/O power’s L+ and M. 
Check that the power terminal block is fully inserted, and the wiring is 
correct. 

IO-Link communication is not working 
COM LED remains lit 

Check that voltage is applied to the Unit power’s 24 V and 0 V and the 
I/O power’s L+ and M. 
Check that the IO-Link Master communication signal (C/Q) and UR-
DS4AD/UR-DS4DA’s C/Q terminal are connected and that the power 
terminal block is fully inserted. 

Check that the IO-Link Master setting is in IO-Link communication mode. 
(For IO-Link Master UR series, check the master parameter "M10. I/O 
function setting")

 

COM LED is flashing at 0.1-second 
intervals 

IO-Link communication has broken off. 
Check the wiring between the IO-Link Master and C/Q. 
Check that the other IO-Link communication line (C/Q) and UR-
DS4AD/UR-DS4DA’s C/Q line are not wired closely for several 
meters or more. 
Check that the power line (inverter or servo motor drive output line) is 
not wired closely for several meters or more. 
Check that the IO-Link master’s power (24 V, 0 V) wiring is not 
separate from UR-DS4AD/UR-DS4DA’s 24 V and 0 V. Be sure to 
connect at least the 0 V for both securely. 
Check that the IO-Link communication line (C/Q) length has not 
exceeded 20 m. 

Range switching is not possible with 
process output data 

Is the setting value (input range) set to specify the range by setting 
value? Check that you have not specified anything other than "0" in 
the index number 74 of the service data. 

ERROR LED is lit 

Is the IO-Link communication once established blocked? 

 

 

 

 

Ramco Innovations                 www.optex-ramco.com                     (800) 280-6933

Summary of Contents for UR-DS4AD

Page 1: ...OPTEX FA IO Link Hub UR DS4AD UR DS4DA User s Manual OPTEX FA CO LTD For technical support and application assistance contact the Optex IO Link experts at Ramco Innovations today Ramco Innovations ww...

Page 2: ...before using UR DS4AD UR DS4DA correctly Also keep this manual in a safe place after reading it and always keep it handy Trademarks and registered trademarks that appear in this manual are the propert...

Page 3: ...communication terminals on the power terminal block 11 Wiring to the analog input output power supply 12 Wiring to the device terminal block for UR DS4AD 12 Wiring to the device terminal block for UR...

Page 4: ...s for UR DS4AD 21 9 Circuit Diagram 22 Analog input circuit diagram for UR DS4AD 22 Analog output circuit diagram for UR DS4DA 22 10 Process Data 23 UR DS4AD 23 Word assignment 24 UR DS4DA 25 Word ass...

Page 5: ...5 Ramco Innovations www optex ramco com 800 280 6933...

Page 6: ...speci es 4 analog output signals to control various actuators with process output data from the IO Link master It can be used to control devices with analog input such as changing the speed of a motor...

Page 7: ...7 3 Dimensions UR DS4AD UR DS4DA 39 9 21 5 Unit mm 85 63 85 63 21 5 39 9 Unit mm Ramco Innovations www optex ramco com 800 280 6933...

Page 8: ...e DIN rail 2 Push the lower side from the front 3 Push the DIN rail mounting hook up to lock the product in place This illustration is for UR DS4AD Install UR DS4AD UR DS4DA at least 10 mm away from a...

Page 9: ...9 5 System Con guration Ramco Innovations www optex ramco com 800 280 6933...

Page 10: ...V and C Q are connected internally with the terminals of the e CON socket Power supply for analog output devices Connecting to the IO Link communication e CON socket See page 11 Connecting to the IO...

Page 11: ...tween AWG 28 to 20 stranded wires with a rated temperature of 75 C or higher Connecting to the IO Link communication terminals on the power terminal block Connect the 0V C Q 24 V terminals on the powe...

Page 12: ...used and recommended ferrule refer to Wire Installation on page 13 Wiring to the device terminal block for UR DS4AD Connect the wires for power supply and input signal of input devices to the 16 chan...

Page 13: ...ength of single or stranded wire should be 10 mm Wire to be used Use wires with a diameter compatible with the terminal blocks Power terminal block 24V 0V L M C Q AWG24 to 12 Use wires with a temperat...

Page 14: ...maged when pulling it out Unit mm Terminal block AWG Ferrules from PHOENIX CONTACT Model Dimensions Insulation sleeve color L1 L2 D1 S1 D2 S2 Device terminal block 24 AI 0 25 8 YE 12 50 8 00 0 80 0 15...

Page 15: ...e pressing the open close key Insert the wire until the tip reaches the bottom 3 Release the open close key to complete wiring Pull gently to make sure it does not come loose Power terminal block For...

Page 16: ...e ferrule is stuck inside the terminal block and cannot be removed the terminal block may be damaged by forceful removal If the ferrule is stuck move the ferrule up down left or right while pressing i...

Page 17: ...nd the shield wire SLD to the analog output device 6 Device terminal block L M Used to supply 24 V power L M to the analog output device 7 Power terminal block 0 V 24 V Supplies unit power 24 V 0 V an...

Page 18: ...V power supply L M to analog input devices 6 Power terminal block 0 V 24 V Supplies unit power 24 V 0 V and output power L M This seven pole removable connector has a pitch of 5 08 mm and a rating of...

Page 19: ...ive 2014 30 EU Environment RoHS Directive 2011 65 EU China RoHS Regulation 32 Applicable standard EN 61131 2 Zone A Company standards Noise resistance Feilen Level 3 cleared Compatible DIN rail TH35 7...

Page 20: ...t voltage 11 V Maximum input current 24 mA Voltage input equivalent impedance 250 5 k ohm Current input equivalent impedance 246 ohm Voltage accuracy 0 30 of F S at ambient temperature of 25 C 1 Tempe...

Page 21: ...typical 8 ppm C 0 0008 C Current accuracy 0 2 of F S at ambient temperature of 25 C Temperature coef cient typical 10 ppm C 0 001 C Input resolution 16 bits Dielectric withstand voltage 500 VAC for o...

Page 22: ...r UR DS4DA GND I 0 to 3 V 0 to 3 Internal circuit 1 2 3 82 K ohm 82 ohm 168 3 K ohm 164 ohm Voltage sensing Voltage output Current output GND Internal circuit 1 2 3 15 ohm 15 ohm 20 ohm 0 01 F 0 01 F...

Page 23: ...input lower byte 6 Channel 0 Analog input upper byte 7 Channel 0 Analog input lower byte Process output data 0 2 Channel 3 Input type 0 0 to 10 V 1 10 to 10 V 2 0 to 5 V 3 0 to 20 mA Channel 2 Input t...

Page 24: ...nel 0 Analog input lower byte N 1 Channel 1 Analog input upper byte Channel 1 Analog input lower byte N 2 Channel 2 Analog input upper byte Channel 2 Analog input lower byte N Channel 3 Analog input u...

Page 25: ...te n 5 Channel 1 Analog output upper byte n 6 Channel 1 Analog output lower byte n 7 Channel 0 Analog output upper byte n 8 Channel 0 Analog output lower byte 1 If index number 74 output range selecti...

Page 26: ...annel 2 Analog output lower byte N 3 Channel 3 Analog output upper byte Channel 3 Analog output lower byte N 4 1 N A Channel 3 output type Channel 2 output type Channel 1 output type Channel 0 output...

Page 27: ...o 0 to 5 V voltage input 4 Sets to 1 to 5 V voltage input 5 Sets to 0 to 20 mA current input 6 Sets to 4 to 20 mA current input Maximum span value 76 0 R W 8 32000 Sets the maximum span value for chan...

Page 28: ...ion time The unit is 7 5 minutes Displayed decimal point position 193 0 R W 4 0 Speci es the decimal point position for the process input data displayed on the IO Link master UR series The rst byte co...

Page 29: ...imum span value for channels 0 to 3 Speci es the value given to the process output data when outputting the maximum value of the output range The rst two bytes are the value for channel 0 1 to 4 2 0 t...

Page 30: ...10 Each channel is set separately Subindex number 1 corresponds to channel 0 Display unit character string 194 1 to 4 R W 6 None Speci es the unit character string for the process input data displayed...

Page 31: ...ater than Maximum span value The minimum span value setting is greater than the maximum span value The span width works as 32000 This event occurs only at startup x1801 The setting value memory write...

Page 32: ...ameter M10 I O function setting COM LED is ashing at 0 1 second intervals IO Link communication has broken off Check the wiring between the IO Link Master and C Q Check that the other IO Link communic...

Page 33: ...process data monitor If the IO Link master is the UR series from OPTEX FA check if the required amount is allocated in M40 Process input data words allocation in the master parameter Check the wiring...

Page 34: ...3 and the GND terminal so check that the analog input wires of the analog input device are wired correctly Check that the bit corresponding to the output range setting of the process output data of t...

Page 35: ...d off Noise on the analog output Select a current input device because the impedance of the receiving equipment is lower with a current input than with a voltage input Alternatively connect a 250 for...

Page 36: ...36 The information in this user s manual is correct as of February 2024 UR DS4_UM E_001_2402 Ramco Innovations www optex ramco com 800 280 6933...

Reviews: