29
UR-DS4DA
Na
m
e
Ind
ex nu
m
be
r
S
ubi
nd
ex
nu
m
be
r
R
ea
d/
W
rit
e*
1
B
ac
kup
S
ubj
ec
t
Dat
a b
yt
e c
ou
nt
De
fau
lt v
al
ue
Se
tu
p v
al
ue
S
et
tin
g D
et
ail
s
System
command
2
0
W
1
-
130
Initialization of setting value
131
Stops IO-Link communication after reverting setting values to
default values (Back-to-Box)
Device lock
12
0
R/W
✓
2
0
0
Unlocks the storage function.
2
Storage function lock.
Tag name
24
0
R/W
✓
32
*2
-
Can be used to set a name for this unit, such as the device
function or installation location.
Type of analog
output
74
0
R/W
✓
4
0
-
Switches the output range for channels 0 to 3. The first byte is
the value of channel 0. See the following for the meaning of
each byte value.
1 to 4
✓
1
0
The output range is switched using process output data.
1
Sets the range to 0 to 10 V voltage output.
2
Sets the range to -10 to 10 V voltage output.
3
Sets the range to 0 to 5 V voltage output.
4
Sets the range to 0 to 20 mA current output.
Maximum span
value
76
0
R/W
✓
8
32000
-
Sets the maximum span value for channels 0 to 3. Specifies the
value given to the process output data when outputting the
maximum value of the output range. The first two bytes are the
value for channel 0.
1 to 4
2
0 to
65535*3
Each channel is set separately. Subindex number 1
corresponds to channel 0.
Minimum span
value
77
0
R/W
✓
8
0
-
Sets the minimum span value for channels 0 to 3. Specifies the
value given to the process output data when outputting the
output range value 0. The first two bytes are the value for
channel 0.
1 to 4
2
-32768
to
32767
Each channel is set separately. Subindex number 1
corresponds to channel 0.
Shift value
78
0
R/W
✓
8
0
-
Sets the shift value for channels 0 to 3. The span is calculated
by adding this shift value to the process output data. The first
two bytes are the value of channel 0.
1 to 4
2
-32768
to
32767
Each channel is set separately. Subindex number 1
corresponds to channel 0.
Internal
temperature
161
0
R
2
-
-2739 to
10461
Returns the temperature on the internal board. The unit is 0.1
°
C.
Operating time
162
0
R
4
0 to
4294967295
Returns the internal operation time. The unit is 7.5 minutes.
Ramco Innovations
www.optex-ramco.com
(800) 280-6933