18
UR-DS
4
DA
No.
Name
Function
(1)
POWER LED (green)
Lights up when power is turned on for the analog output device.
(2)
COM LED (green)
Illuminated
: After startup, before IO-Link communication is established
1 second on 0.1 second off
: IO-Link communication established
0.55 second on 0.55 second off
: Find me
0.1 second on 0.1 second off
: IO-Link communication cutoff
(3)
ERROR LED (Red)
Turns on when IO-Link communication stops or some other error occurs.
(4)
Output range LED (orange)
Turns on/off based on the analog output range of each channel.
(5)
Device terminal block
(A, GND, L+, M)
Connects analog output signals (A0 to A3, GND) and 24V power supply
(L+, M) to analog input devices.
(6)
Power terminal block
(0 V, +24 V)
Supplies unit power (+24 V, 0 V) and output power (L+, M).
This seven-pole removable connector has a pitch of 5.08 mm and a
rating of 12 A.
It is wired in parallel with the input power supply.
Unit power (+24 V, 0 V) and C/Q are wired to the IO-Link master, and unit
power is supplied by the IO-Link master.
Unit power (+24 V, 0 V) and C/Q are connected internally with the
terminals of the e-CON socket, and either the power terminal block or e-
CON socket can be connected to the IO-Link master.
(7)
e-CON socket (4-poles)
Unit power (+24 V, 0 V) and C/Q can be wired to the IO-Link master via
the e-CON socket.
(8)
DIN rail mounting hook
Slides for attaching/removing the product to/from the DIN rail.
(1)
(4)
(5)
(6)
(8)
(2)
(3)
(7)
Ramco Innovations www.optex-ramco.com (800) 280-6933