P/N 315-049594-1 

7

 

Trouble Indications 

All panels and network annunciators connected to the network will indicate network specific faults (see Section III for 
details).  Individual panel system troubles (ground fault, battery, etc) will not be transmitted to other fire panels but will 
be transmitted to the RND-2s, network printers and simple monitoring computers. 
 
All initiating devices on the MPC-6000 or MPC-7000 can also be programmed to a network LINK (accomplished while 
configuring devices on the panel).  The maximum LINK number for the MPC-6000 and MPC-7000 is 255.  If an 
initiating device on a panel goes into trouble, and it has been programmed to a network LINK, it will send a network 
message to the other panels indicating that the network LINK is in trouble.  If other panels on the network have that 
LINK number programmed, they will also indicate the trouble as configured. 
 

Other panels will display: 

Explanation of display/history event: 

 TRB   xxx/yyy 10:12 
40 character custom 
link message 
NN:L175 NETWORK LINK 

This is x of y troubles in the system that was logged at 10:12 (24 hour time) 
These two lines will indicate a custom message for the network link 
 
Bottom line indicates that node link 175 on node nn is the source of the 
trouble.  The plus sign at the end indicates that there are more 

RND-2s will display: 

Explanation of display/history event:

 

 TRB   xxx/yyy 10:12 
40 character custom 
link message 
NN:xxxx Device type

 

The RND-2 if configured for this will also show the individual point information. 

 
When the trouble event has been restored, the display will show below; 
 

Other panels will display: 

Explanation of display/history event: 

 R/TRB xxx/yyy 10:12 
40 character custom 
link message 
NN:L175 NETWORK LINK 

This is a restoral of x of y troubles in the system that was logged at 10:12 (24 
hour time) 
These two lines will indicate a custom message for the network link 
 
Bottom line indicates that node link 175 on node nn is the source of the 
trouble.  The plus sign at the end indicates that there are more 

RND-2s will display: 

Explanation of display/history event:

 

 R/TRB xxx/yyy 10:12 
40 character custom 
link message 
NN:xxxx Device type

 

The RND-2 if configured for this will also show the individual point information 
for the trouble restoral. 

 
 

firealarmresources.com

Summary of Contents for MPC-NET2

Page 1: ...Inc 8 Fernwood Road Florham Park NJ 07932 Tel 973 593 2600 Fax 973 593 6670 Web www faradayfirealarms com P N 315 049594 1 MPC NET2 MPC Net System Networking Owner s Manual 315 049594 Revision 1 0 03...

Page 2: ...P N 315 049594 1 2 This page is intentionally blank firealarmresources com...

Page 3: ...le indications 7 Supervisory Indications 8 Alarms Indications 8 II NETWORK ANNUNCIATORS 9 RND 2 9 III NETWORK TROUBLESHOOTING 11 NIB LED INDICATORS 11 NETWORK SPECIFIC TROUBLES 12 IV WIRING DIAGRAMS 1...

Page 4: ...P N 315 049594 1 4 firealarmresources com...

Page 5: ...both of the network ports of an A version NIB to use fiber media instead of Category 5 wire with the use of optional fiber converters 12535 or 12536 Each converter converts one port of the NIB to fibe...

Page 6: ...2 Send global commands 1 yes 0 no For RND 2 only The NIB configuration data is passed from the panel to the NIB at power up and reset of the panel Printer NIB Configuration For wiring connections ref...

Page 7: ...es in the system that was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trou...

Page 8: ...hat was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trouble The plus sign...

Page 9: ...bally or for the RND 2 only Alarms may also be silenced globally The RND 2 has the ability to reset all panels on the network or just the RND 2 There is also a network event history that can be retrie...

Page 10: ...P N 315 049594 1 10 firealarmresources com...

Page 11: ...e FA panel or annunciator It should blink every couple of seconds when the NIB is connected to a FA panel or annunciator If the NIB is connected to a printer this LED will only blink when data is bein...

Page 12: ...nel showing this message is not communicating with its NIB NW Ring Broken The network is not physically in tact NW Forward Link Port 2 of the attached NIB has lost the link with port 1 of the next NIB...

Page 13: ...e installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Category 5 wire with...

Page 14: ...P N 315 049594 1 14 firealarmresources com...

Page 15: ...P N 315 049594 1 15 firealarmresources com...

Page 16: ...t be daisy chained from network interface board to network interface board 3 Use Category 5 wire with 3000 feet maximum distance from network interface module to network interface module Step 1 Instal...

Page 17: ...otes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Cate...

Page 18: ...P N 315 049594 1 18 99 firealarmresources com...

Page 19: ...mounts inside the MPC 6000 cabinet Notes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board...

Page 20: ...r printers as described earlier in the wiring diagram section 3 Attach Duplex fiber to Converter using the ST connectors on the Converter For the 12536 Single Mode Converter 1 Install on NIB carefully...

Page 21: ...event the output coding may be selected Local Panel Output Zone mapping MPC 6000 7000 panel up to 99 panels Group XX Up to Group 240 T 22 1 32 12 U U U U C T Input group 1 Group 2 Local Panel Output Z...

Page 22: ...P N 315 049594 1 22 firealarmresources com...

Page 23: ...P N 315 049594 1 23 firealarmresources com...

Page 24: ...P N 315 049594 1 firealarmresources com...

Reviews: