P/N 315-049594-1
13
IV. WIRING DIAGRAMS
12523A NETWORK INTERFACE BOARD
The 12523 or 12523A Network Interface Board is a module to interface between the MPC-6000 or MPC-
7000 Fire Alarm System Control Unit or the RND-2 Remote Network Display. The NIB mounts to a 6-
gang box, 2” deep minimum. The Faraday 12411 surface backbox or the 12525 surface backbox with
transient suppressor may be used for surface mounting.
12523 / 12523A Dimensions
12525 Dimensions
12523 / 12523A Wiring
Notes:
1.)
Units to be installed in accordance with all local codes.
2.)
T-Tapping is not allowed. Communication wiring must
be daisy chained from network interface board to
network interface board.
3.) Use Category 5 wire with 3000 feet maximum distance
from network interface module to network interface
module.
4.)
12525 is required when network wiring leaves the
building.
FROM PREVIOUS
FROM PREVIOUS
NIB
TO NEXT NIB
TO NEXT NIB
FRAME GROUND
FRAME GROUND
FROM MPC-6000 OR
MPC-7000 FIRE
ALARM CONTROL
PANEL OR RND-2
FROM MPC-6000 OR
MPC-7000 FIRE
ALARM CONTROL
PANEL OR RND-2
TO MPC-6000 OR
MPC-7000 FIRE
ALARM CONTROL
PANEL OR RND-2
TO MPC-6000 OR
MPC-7000 FIRE
ALARM CONTROL
PANEL OR RND-2
firealarmresources.com
Summary of Contents for MPC-NET2
Page 2: ...P N 315 049594 1 2 This page is intentionally blank firealarmresources com...
Page 4: ...P N 315 049594 1 4 firealarmresources com...
Page 10: ...P N 315 049594 1 10 firealarmresources com...
Page 14: ...P N 315 049594 1 14 firealarmresources com...
Page 15: ...P N 315 049594 1 15 firealarmresources com...
Page 18: ...P N 315 049594 1 18 99 firealarmresources com...
Page 22: ...P N 315 049594 1 22 firealarmresources com...