P/N 315-049594-1 

17

 

12526A NETWORK INTERFACE BOARD WITH 
ISOLATED RS232 PORT 

The 12526 or 12526A Network Interface Board with an isolated RS232 port is for hooking up a printer or 
computer to the network. The NIB mounts to a 6-gang box, 2” deep minimum.  The Faraday 12411 
Surface Backbox or the 12525 Surface Backbox with Transient Suppressor may be used for surface 
mounting. 
 

 

 

 
 
 
 
 
 
 
 

 

12526 / 12526A Dimensions

12525 Dimensions

 

12526 / 12526A Wiring

 

 
Notes: 
 
1.) 

Units to be installed in accordance with all local codes. 

2.) 

T-Tapping is not allowed.  Communication wiring must 

          be daisy chained from network interface board to    
          network interface board. 
3.)      Use Category 5 wire with 3000 feet maximum distance 
          from network interface module to network interface 
          module. 
4.) 

12525 is required when network wiring leaves the  

 building. 
 

FRAME GROUND

FRAME GROUND

FROM MPC-6000 OR

MPC-7000 FIRE

ALARM CONTROL

PANEL OR RND-2

FROM MPC-6000 OR

MPC-7000 FIRE

ALARM CONTROL

PANEL OR RND-2

TO PRINTER OR COMPUTER

TO PRINTER OR COMPUTER

TO NEXT NIB

TO NEXT NIB

FROM PREVIOUS

FROM PREVIOUS

NIB

firealarmresources.com

Summary of Contents for MPC-NET2

Page 1: ...Inc 8 Fernwood Road Florham Park NJ 07932 Tel 973 593 2600 Fax 973 593 6670 Web www faradayfirealarms com P N 315 049594 1 MPC NET2 MPC Net System Networking Owner s Manual 315 049594 Revision 1 0 03...

Page 2: ...P N 315 049594 1 2 This page is intentionally blank firealarmresources com...

Page 3: ...le indications 7 Supervisory Indications 8 Alarms Indications 8 II NETWORK ANNUNCIATORS 9 RND 2 9 III NETWORK TROUBLESHOOTING 11 NIB LED INDICATORS 11 NETWORK SPECIFIC TROUBLES 12 IV WIRING DIAGRAMS 1...

Page 4: ...P N 315 049594 1 4 firealarmresources com...

Page 5: ...both of the network ports of an A version NIB to use fiber media instead of Category 5 wire with the use of optional fiber converters 12535 or 12536 Each converter converts one port of the NIB to fibe...

Page 6: ...2 Send global commands 1 yes 0 no For RND 2 only The NIB configuration data is passed from the panel to the NIB at power up and reset of the panel Printer NIB Configuration For wiring connections ref...

Page 7: ...es in the system that was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trou...

Page 8: ...hat was logged at 10 12 24 hour time These two lines will indicate a custom message for the network link Bottom line indicates that node link 175 on node nn is the source of the trouble The plus sign...

Page 9: ...bally or for the RND 2 only Alarms may also be silenced globally The RND 2 has the ability to reset all panels on the network or just the RND 2 There is also a network event history that can be retrie...

Page 10: ...P N 315 049594 1 10 firealarmresources com...

Page 11: ...e FA panel or annunciator It should blink every couple of seconds when the NIB is connected to a FA panel or annunciator If the NIB is connected to a printer this LED will only blink when data is bein...

Page 12: ...nel showing this message is not communicating with its NIB NW Ring Broken The network is not physically in tact NW Forward Link Port 2 of the attached NIB has lost the link with port 1 of the next NIB...

Page 13: ...e installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Category 5 wire with...

Page 14: ...P N 315 049594 1 14 firealarmresources com...

Page 15: ...P N 315 049594 1 15 firealarmresources com...

Page 16: ...t be daisy chained from network interface board to network interface board 3 Use Category 5 wire with 3000 feet maximum distance from network interface module to network interface module Step 1 Instal...

Page 17: ...otes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board to network interface board 3 Use Cate...

Page 18: ...P N 315 049594 1 18 99 firealarmresources com...

Page 19: ...mounts inside the MPC 6000 cabinet Notes 1 Units to be installed in accordance with all local codes 2 T Tapping is not allowed Communication wiring must be daisy chained from network interface board...

Page 20: ...r printers as described earlier in the wiring diagram section 3 Attach Duplex fiber to Converter using the ST connectors on the Converter For the 12536 Single Mode Converter 1 Install on NIB carefully...

Page 21: ...event the output coding may be selected Local Panel Output Zone mapping MPC 6000 7000 panel up to 99 panels Group XX Up to Group 240 T 22 1 32 12 U U U U C T Input group 1 Group 2 Local Panel Output Z...

Page 22: ...P N 315 049594 1 22 firealarmresources com...

Page 23: ...P N 315 049594 1 23 firealarmresources com...

Page 24: ...P N 315 049594 1 firealarmresources com...

Reviews: