P/N 315-049594-1
16
12525 LINE SURGE SUPPRESSOR
The 12525 is a data line Surge Suppressor and is required when networking from building to building
using Category 5 wiring. The 12525 Surge Suppressor comes mounted in a surface backbox and can be
used with a 12523A or 12526A Network Interface Board for mounting.
Notes:
1.) Units to be installed in accordance with all local
codes.
2.) T-Tapping is not allowed. Communication wiring
must be daisy chained from network interface board to
network interface board.
3.) Use Category 5 wire with 3000 feet maximum distance
from network interface module to network interface
module.
Step 1.) Installation is to be done by qualified
personnel who have thoroughly read and
understood this instruction sheet.
Step 2.) Disconnect BATTERY and AC prior to
working on equipment.
Step 3.) Mount 6-gang backbox as required (see
mounting
below).
Step 4.) Attach conduit and run wires as required.
Step 5.) Attach unit to backbox, using four #6 x ½”
screws.
Step 6.) Apply power to system.
Step 7.) Check for proper operation of functions.