INSTALLATION INSTRUCTION AND WIRING FOR
CAT. NO. 15217 AUXILIARY RELAY MODULE
Parts Supplied
1
15217
Auxiliary Relay Module
4
P8387-11 Spacer #10- 3/8"
4
18965
Keps Nut #6-32
1
444466
Cable and Connector
Ass'y
1
444733
Instruction Sheet
The 15217 Auxiliary Relay Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System
Control Unit. This module provides a form "C" trouble contact and a form "C" general alarm contact. The
module also contains a disconnect switch and a yellow trouble / off-normal switch L.E.D. The disconnect switch
may be activated during testing or servicing of the system to prevent transfering the general alarm contacts. (a
trouble output will be generated upon activation of the disconnect switch).
Module Mounting Diagram
Step 1.)
Installation is to be done only by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.)
Disconnect all power into system, including batteries.
Step 3.)
Install module to left side of cabinet.
A.) Place four - #10-3/8" spacers (P/N P8397-11) over
studs on the left side of the cabinet.
B.) Mount module with terminal block towards front
cover.
C.) Use four - #6-32 keps nuts (P/N 18965) to secure
module in place.
D.) Plug cable and connector ass'y (P/N 444466) into
the module connector J1 and main board
connector J4 with the colored rib on the dot at both
ends.
CAUTION: Check to see that the connectors are
properly seated on all of the pins.
Step 4.)
Connect field wires as required.
Step 5.)
Apply power to system.
Step 6.)
Check for proper operation of module functions.