III-
19
COMPATIBLE 4-WIRE SMOKE DETECTORS
FOR 15220A AND 15240A FIRE ALARM CONTROL PANELS
Compatible 4-Wire Smoke Detectors must have a minimum absolute voltage range of 19 to 28 V.D.C.
DECTECTOR
MANUFACTURER
MAXIMUM
MAXIMUM
W/BASE
DETECTOR
STANDBY
ALARM
ORDER NO.
W/BASE
CURRENT
CURRENT
NOTES
AIR PRODUCTS & CONTROLS
9269
RW-DC-N
0.081ma.
115ma.
MUST USE EOL RELAY
9270
RW-DC-P
0.110ma.
115ma.
MUST USE EOL RELAY
APOLLO FIRE DETECTORS LIMITED
9260 w/9266
55000-350 w/46281-227
0.130ma.
100ma.
MUST USE EOL RELAY
9261 w/9266
55000-250 w/46281-227
0.081ma.
100ma.
MUST USE EOL RELAY
9264 w/9266
55000-153 w/46281-227
0.086ma.
100ma.
MUST USE EOL RELAY
9274 w/9266
55000-152 w/46281-227
0.096ma.
100ma.
MUST USE EOL RELAY
9259 w/9266
55000-150 w/46281-227
0.086ma.
100ma.
MUST USE EOL RELAY
9221 w/9266
55000-151 w/46281-227
0.086ma.
100ma.
MUST USE EOL RELAY
9222 w/9266
55000-380 w/46281-227
0.205ma.
100ma.
MUST USE EOL RELAY
DETECTION SYSTEMS, INC. (DSI)
9195 W/9198
DS200 W/MB200-4W
0.025ma.
36ma.
MUST USE EOL RELAY
9196 W/9198
DS200HD W/MB200-4W
0.025ma.
36ma.
MUST USE EOL RELAY
KIDDE-FENWAL INC.
9472 W/9488
PSD7125 W/
0.100ma.
20ma.
MUST USE EOL RELAY
70-201000-101
35ma.
w/Remote LED
9473 W/9488
PSD7126 W/
0.100ma.
20ma.
MUST USE EOL RELAY
70-201000-101
35ma.
w/Remote LED
9474 W/9489
PSD7129 W/
40ma.
100ma.
MUST USE EOL RELAY
DH-22
OR 6 WIRES
9475 W/9488
PSD7130 W/
0.100ma.
20ma.
MUST USE EOL RELAY
70-201000-101
35ma.
w/Remote LED
9476 W/9488
PSD7131 W/
0.100ma.
20ma.
MUST USE EOL RELAY
70-201000-101
35ma.
w/Remote LED
9495 W/9488
CPD7021 W/
0.060ma.
20ma.
MUST USE EOL RELAY
70-201000-101
35ma.
w/Remote LED
9495 W/9489
CPD7021 W/
40ma.
100ma.
MUST USE EOL RELAY
DH-22
OR 6 WIRES
HOCHIKI-AMERICA CORP. ALPHA-LARM DIV.
9225 W/9230
SLK-24F W/HS-2RB/4
0.200ma.
26ma.
MUST USE EOL RELAY
9226 W/9230
SLK-24FH W/HS-2RB/4
0.200ma.
26ma.
MUST USE EOL RELAY
9227 W/9230
SIF-24F W/HS-2RB/4
0.200ma.
26ma.
MUST USE EOL RELAY
9228 W/9230
SIH-24F W/HS-2RB/4
0.200ma.
26ma.
MUST USE EOL RELAY
9234
AL-HADH-UP4
0.200ma.
26ma.
MUST USE EOL RELAY
9233
AL-SPA-24B
0.25ma.
40ma.
MUST USE EOL RELAY
AND 6 WIRES
firealarmresources.com