IV - 3
TROUBLESHOOTING GUIDE
(Cont'd)
INDICATOR
POSSIBLE PROBLEMS
POSSIBLE SOLUTIONS
Option Module Troubles
15212 Remote Annunciator Module
Trouble
1.) Open annunciator wiring
1.) Correct wiring fault
2.) Activated annunciator indicator
2.) A.) Operate SYSTEM RESET switch
B.) Return the anunciator LAMP
TEST switch to normal
15209 City Tie Module
Trouble
1.) DISCONNECT switch operated
1.) Return the DISCONNECT switch
to normal
15215 City Tie/Auxiliary Relay Module
Trouble
1.) DISCONNECT switch operated
1.) Return the DISCONNECT switch
to normal
2.) Jumpers not programmed properly
2.) See Installation Installations
If programmed for Local Energy City tie
3.) Tripped city box
3.) Reset city box
4.) Open city box wiring
4.) Correct wiring fault
15206 D.A.C.T. Interface Module
1.) Disconnect switch operated
1.) Return the disconnect switch
to normal.
2.) Fuse F1 blown
2.) Replace with proper fuse.