III-
11
TYPICAL INITIATING DEVICE WIRING DIAGRAM
SUPERVISORY SWITCHES
Notes:
1.)
This wiring diagram only shows general
information about the initiating device. For
specific wiring and installation information
read the instructions provided with each
device.
2.)
For initiating circuit specifications see the
15220A Wiring Diagram (445928) or the
15240A Wiring Diagram (445929).
END OF LINE RESISTOR
(3.9K OHM 1/2 WATT)
SUPERVISORY SWITCH
FARADAY CAT. NO.
PM6223, PM6224,
PM6781, PM6782
SYSTEM SENSOR CAT. NO.
OSY2, P1BV2, EPS40-1, EPS40-2
SUPERVISORY SWITCH
Note:
When Sprinkler Supervisory Switches are used,
they should be connected to Zone #1 as shown.
Diodes D27, D30 and D31 must also be cut out
of the main Board.
INITIATING
CIRCUIT #1
firealarmresources.com