1 2 5 3 0 / 1 2 5 4 0 O W N E R ' S M A N U A L
P/N 447203 Issue I
V-9
Style 6 provides redundant communication paths.
ADDRESSABLE DEVICE CIRCUIT
WIRING / OPERATION COMPARABLE TO NFPA STYLE “6”
Note:
Faraday Addressable Devices:
Detectors, Monitor Modules, or Control Modules up to a maximum of 60 devices per addressable
device circuit. Maximum of 20 devices between Isolator Modules. Maximum of 12 Isolator
Modules per addressable device circuit.
System Sensor Addressable Devices:
Sensors, Monitor Modules, or Control Modules up to a maximum of 99 Sensors and 99 Modules
per addressable device circuit. Recommended maximum of 25 devices between Isolator
Modules.
SUPERVISED,
POWER LIMITED