FARADAY, LLC
447153 ISSUE I REV. A
PAGE 1 OF
4
INSTALLATION INSTRUCTIONS AND WIRING FOR
DACT EXPANSION MODULE
CAT. NO. DEM-1 P/N 12513
The 12513 DACT Expansion Module is an optional module for the 12500, 12530 or 12540 Fire Alarm
System Control Unit. The DACT (Digital Alarm Communicator Transmitter) Expansion Module provides
telephone line connections for communication with a DACR (Digital Alarm Communicator Receiver). The
DACT Expansion Module options are set through the control unit programming sequence. One DACT
Expansion Module may be mounted in the enclosure above the Main Termination Board. If more than one
expansion board is used, the extended enclosure is required.
PARTS SUPPLIED
1
413752
DACT Expansion Board
1
413699
DACT Board
4
942456
Spacers, 5/8”
6
29529-11
Screws, #6-32x1/4”
1
446651
Cable Assembly, 34 pin 12”
1
447153
Instruction Sheet
12513 MOUNTING
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect all pow er into system, including
batteries.
Step 3.) Mount DACT Board as shown, using four
spacers (P/N 942456) to the DACT Board.
NOTE: The DACT Board connector J1 must be
aligned with the DACT Expansion Board
header P1 below.
Step 4.) Mount DACT Expansion Board using six screws
(P/N 29529-11) as shown.
NOTE: The DACT Expansion Board connector P2
must be aligned with the circuit board
connector below.
Step 5.) Attach ground wire under lower right mounting
screw.
Step 6.) Connect cable assembly (P/N 446651) from the
Main Logic Board connector P1 or the previous
expansion board connector to the DACT
Expansion Board connector P4.
Step 7.) Attach conduit and run wires as required.
Step 8.) Connect wires to the fire alarm system control
unit as required.
Step 9.) Apply power to system.
Step 10.) Program for proper operation of functions.
a) Tech Level>>Outputs>Option Mods>DACT CFG
(Set DACT line and general configurations)
b) Tech Level>>Outputs>Option Mods>DACT ACCTS
(Set DACT account configurations)
c) Maint Level>>Disable/Enable>Outputs>DACT
>Enabled
NOTE: See Programmer’s Manual (P/N 447081 for
12500 or 447207 for 12530/12540) for
more details on programming.
Step 11.) Check for proper operation of functions.
DACT Board
Main Termination Board
Screws
(6)
DACT
Expansion
Board
Spacers (4)