WIRING SEPARATION
All high voltage and non-power limited wiring must be kept separate from power limited wiring. A ¼”
separation must be maintained, with high voltage and non-power limited wiring running in separate
conduit openings from power limited wiring.
E
C
A
B
H
F
A.
Non-power limited - High Voltage
(AC power) or B
B.
Non-power limited - High Voltage
(AC power) or A
C.
Power limited (or E or F or H)
D.
Non-power limited
(Battery If external enclosure required)
E.
Power limited (or C or F or H)
F.
Power limited (or C or E or H)
G.
Non-power limited
(Local Energy or Shunt City Tie)
H.
Power limited (or C or E or F)
D
G
1.
Main Termination Board
2.
12522 Loop Driver Board
3.
12401A Class A Adapter
4.
12503 Conventional Expansion Board
5.
12505 Loop/Signal Expansion
6.
12504 Class A Adapter
7.
12402 Relay Board
8.
12511 Serial Isolation Board
9.
12513 DACT Expansion Module