FARADAY, LLC
446060 ISSUE I REV. B
PAGE 1 OF 2
INSTALLATION INSTRUCTIONS AND WIRING FOR
DIGITAL COMMUNICATOR CABLE
CAT. NO. DCC-1 P/N 12410
The 12410 Digital Communicator Cable is required when the 15128 Digital Communicator is used with the
12400, 12500, 12530 or 12540 Fire Alarm System Control Unit. The 15128 is mounted to the right side of
the enclosure and the cable assemblies interface from the control unit to the communicator.
PARTS SUPPLIED
1
446353
Cable Assembly
2
29529-11
Screw, #6-32x1/4”
1
18965
Keps Nut, #6-32
1
446060
Instruction Sheet
15128 MOUNTING
15128 WIRING
PHONE LINE 1
PHONE LINE 2
POWER
24VDC
CHANNEL INPUTS
RELAY
CONNECT
RKP-100
CONNECT
TO AUX. POWER
OUPUT (RED TO + &
BLACK TO -)
CABLE ASEMBLY TO P7 ON
MAIN TERMINATION BOARD
OR P1 ON ALARM RELAY
TO TELEPHONE LINES
NOTES:
1.)
Units to be installed in accordance with all local
electrical codes.
2.)
See DC-100 / DC-101 Installation Manual P/N
445833 for further installation details.
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect all power into system, including
batteries.
Step 3.) Mount the digital communicator as shown, using
two screws (P/N 29529-11) to the stand-offs
provided at the right side of the backbox The
terminal blocks for telephone connections must
be towards the bottom of the backbox.
Step 4.) Attach the green ground wire to the stud located
below the digital communicator. Secure with a
#6-32 keps nut (P/N 18965).
Step 5.) Connect cable assembly (P/N 446353) from the
12400 Main Termination Board connector P7 or
12500 Main Termination Board connector P11 to
the digital communicator connectors P2 (Channel
Inputs) and P5 (Low AC Inputs) and relay
terminals (Black to common and white to N.O.).
NOTE: If the Alarm Relay Board is used, then
plug the cable into connector P1 on the
Alarm Relay Board, instead of P7 on the
Main Termination Board.
Step 6.) Connect power cable assembly, provided with
the digital communicator, from the digital
communicator connector P1 (DC Power) to the
auxiliary power output (Red to + and Black to -)
on the Main Termination Board.
Step 7.) Attach conduit and run telephone wires as
required.
Step 8.) Apply power to system.
Step 9.) Program the digital communicator with the 15403
programmer as required.
NOTE: Use the following settings for proper operation:
ZONE ACTIVE=Active low input
ZONE SUPERVISED=No
ALARM CHANNEL INPUT TYPE=Fire
TROUBLE CHANNEL INPUT TYPE=Fire
SUPERVISORY CHANNEL=Sprinkler
CHANNEL RESPONSE #1=0.3 to 0.4 sec
CHANNEL RESPONSE #3=0.3 to 0.4 sec
CHANNEL RESPONSE #4=0.3 to 0.4 sec
RELAY #1=Trouble
DIALER TYPE=USA
AC MONITORING=Active low
AC LOSS HOURS=6-12 for Central Station Service
15 for Remote Station Service
Step 10.) Check for proper operation of functions.