This protection function is adjusted by setting three different parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
78
Out of step
Permission
-
-
Yes/No
-
No
Level
1
25
1
°
10
Reset time
0,02
300,00
0,01
s
0,20
If Δɸ exceeds the value adjusted in “level” setting, the function activates (trips)
immediately. The accuracy is ± 5 °.
4.10. Function 52. Circuit Breaker monitoring
This function allows the status of the circuit breaker to be monitored and preventive
maintenance to be performed, for which the following parameters need to be configured:
Group
Description
Minimum
Maximum
Step
Unit
Default
52
Circuit breaker monitoring
Maximum number of openings
1
10000
1
-
10
Opening time
0,02
30,0
0,01
s
0,10
Closing time
0,02
30,0
0,01
s
0,10
Maximum repeated openings
1
10000
1
-
3
Time of maximum repeated openings
1,00
300,0
0,01
min
9,00
Summary of Contents for SIL-V
Page 7: ...www fanox com Rev 10 7 212 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 8: ...www fanox com Rev 10 8 212 2 2 Equipment dimensions...
Page 9: ...www fanox com Rev 10 9 212 2 3 Cut out pattern...
Page 11: ...www fanox com Rev 10 11 212 3 VT configuration phase neutral...
Page 12: ...www fanox com Rev 10 12 212 3 VT configuration phase neutral residual voltage SILVxxxx0xxxxx...
Page 13: ...www fanox com Rev 10 13 212 3 VT configuration phase neutral busbar voltage SILVxxxx2xxxxx...
Page 14: ...www fanox com Rev 10 14 212 3VT configuration phase phase residual voltage...
Page 15: ...www fanox com Rev 10 15 212 2VT configuration phase phase residual voltage...
Page 17: ...www fanox com Rev 10 17 212 2 5 Terminals...
Page 25: ...www fanox com Rev 10 25 212 3 3 Functional Diagram...
Page 192: ...www fanox com Rev 10 192 212...
Page 211: ...www fanox com Rev 10 211 212 NOTES...
Page 212: ...www fanox com Rev 10 212 212...