Rev.10
30/212
4.7.
Function 81O/U. Overfrequency and underfrecuency protection
There are four protection units of the variation in frequency. Each one of them has an
adjustment which determines whether the unit acts as overfrequency or underfrequency.
The reaction time of the unit is determined by the set operating time.
In case the unit acts like overfrequency, activation of the function occurs at 100%
frequency level set and is reset when the measured frequency is 50 mHz lower than set
start level.
If the unit is set as underfrequency, activation of the function occurs at 100% frequency
level set and is reset when the measured frequency is 50 mHz higher than set start level.
The reset is temporized and the reset time is determined by the reset time setting.
The frequency measurement is done from the voltage of phase B. It takes a minimum of
45 volts at this stage for 81 functions to be operational. If the measured phase voltage is
less than 45 volts, it activates a state bit indicating function blocked. When the frequency
measurement is again valid, function begins in the start state with all bits and counters
reset.
This protection function is adjusted by setting five different parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
81_1
81_2
81_3
81_4
Overfrequency or Underfrequency
Permission
-
-
Yes/No
-
No
Type
-
-
(1*)
-
Overfrequency
Activation level
45.00
65.00
0.01
Hz
50.20
Operating time
0.06
300.00
0.01
s
0.15
Reset time
0,02
300,00
0,01
s
0,20
(1*) Overfrequency or Underfrequency
The frequency measurement is an average value of the frequency measured during 8
cycles. The tripping time will be the adjusted value plus the necessary time to achieve the
measure during 8 cycles
Summary of Contents for SIL-V
Page 7: ...www fanox com Rev 10 7 212 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 8: ...www fanox com Rev 10 8 212 2 2 Equipment dimensions...
Page 9: ...www fanox com Rev 10 9 212 2 3 Cut out pattern...
Page 11: ...www fanox com Rev 10 11 212 3 VT configuration phase neutral...
Page 12: ...www fanox com Rev 10 12 212 3 VT configuration phase neutral residual voltage SILVxxxx0xxxxx...
Page 13: ...www fanox com Rev 10 13 212 3 VT configuration phase neutral busbar voltage SILVxxxx2xxxxx...
Page 14: ...www fanox com Rev 10 14 212 3VT configuration phase phase residual voltage...
Page 15: ...www fanox com Rev 10 15 212 2VT configuration phase phase residual voltage...
Page 17: ...www fanox com Rev 10 17 212 2 5 Terminals...
Page 25: ...www fanox com Rev 10 25 212 3 3 Functional Diagram...
Page 192: ...www fanox com Rev 10 192 212...
Page 211: ...www fanox com Rev 10 211 212 NOTES...
Page 212: ...www fanox com Rev 10 212 212...