Rev.17
24/119
The following states are associated with this function:
Function
State
Description
52
Start
Energized/De-energized
These are the different states of the circuit
breaker automatic control
Error
Open
Opening time
Opening fault
Closed
Closing time
Closing fault
No. of configured openings exceeded
Activated if the meter that measures the number
of openings exceeds the "Excessive number of
openings" setting
No. of configured accumulated (l2t) amps exceeded
Activated if the accumulated amps meter
exceeds "Maximum accumulated amps" setting
Repeated Trips
Activated if the number of openings exceeds the
setting in "Excessive repeated openings" for the
time set in "Time of excessive repeated
openings"
52a
-
52b
-
The circuit breaker performance is shown in the following finite state machine:
The way that the circuit breaker is monitored becomes more or less complex depending on whether it
is fitted with no breaker contacts, one breaker contact (52a or 52b) or both (52a and 52b).
If no breaker contacts are used, the monitoring of the circuit breaker is made through the current
measurement. This is, if less than 8% of rated current is detected it is considered the breaker is open
and if more than 10% of rated current is available, it is considered the breaker is closed.
If only the circuit breaker 52a contact is available, it should be wired to the corresponding physical
input. This physical input is then assigned to the "52a” logic signal. The 52b logic signal is calculated
internally as the negative of 52a.
If only the circuit breaker 52b contact is available, it should be wired to the corresponding physical
input. This physical input is then assigned to the "52b” logic signal. The 52a logic signal is calculated
internally as the negative of 52b.
Summary of Contents for SIA-F
Page 7: ...www fanox com Rev 17 7 119 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Frontal view...
Page 8: ...www fanox com Rev 17 8 119 2 2 Case dimensions The dimensions are in mm CUT OUT PATTERN...
Page 9: ...www fanox com Rev 17 9 119 2 3 Connection diagram 3 Phase CT and neutral CT Connection...
Page 10: ...www fanox com Rev 17 10 119 3 Phase CT and residual neutral Connection...
Page 34: ...www fanox com Rev 17 34 119...
Page 35: ...www fanox com Rev 17 35 119...
Page 36: ...www fanox com Rev 17 36 119...
Page 118: ...www fanox com Rev 17 118 119 NOTES...
Page 119: ...www fanox com Rev 17 119 119...