3.5.
Phase CT and neutral CT selection
The following table shows a summary of phase and neutral CT combinations:
Model
Phase
Neutral
Phase range
Neutral range
SIAF55
CT 5 A
Residual phase connection
0,5-150 A
0,5-150 A
SIAF11
CT 1 A
Residual phase connection
0,1-30 A
0,1-30 A
SIAF51
CT 5 A
CT 1 A
0,5-150 A
0,1-30 A
SIAF1B
CT 1 A
CT 0,2 A
0,1-30 A
0,02-6 A
SIAF5B
CT 5 A
CT 0,2 A
0,5-150
0,02-6 A
In order to assure a correct running of the relay, it is necessary to use the proper current transformer.
Therefore, the load of measurement circuits of the relay and the load of connection cables between
CT’s and relay must be considered.
3.5.1. External current transformers advantages
It is possible to make the connection by passing the cables through the SIAF current transformers.
This solution offers more versatility because the transformation relationship can be modified.
By means of giving turns through the four current transformers of SIAF relay, CT transformation
relationship can be modified getting an easier way of relay adaptation to the final application.
i.e.
If there is a CT with Transformation relationship RT and the secondary of the CT is /1, a relay for
measurement collecting of 1 A of nominal current must be used. However, what is the necessary
action if there is a relay of 5 A of nominal current?
It is possible to give 5 turns to the secondary of the transformers of SIAF relay. Therefore, the
measurement will be multiplied by five and it would be suitable for the 5 A relay. In this case, the new
transformation relationship would be RT/5 and the relay must be adjusted accordingly with the aim of a
correct display of line current.
PRECISION
BURDEN
RELAYS
5P10
5P20
5P30
0,5 VA
0,5 VA
0,5 VA
SIA-F/1
SIA-F/1
SIA-F/1
5P10
5P20
5P30
1 VA
1 VA
1 VA
SIA-F/5
SIA-F/5
SIA-F/5
Summary of Contents for SIA-F
Page 7: ...www fanox com Rev 17 7 119 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Frontal view...
Page 8: ...www fanox com Rev 17 8 119 2 2 Case dimensions The dimensions are in mm CUT OUT PATTERN...
Page 9: ...www fanox com Rev 17 9 119 2 3 Connection diagram 3 Phase CT and neutral CT Connection...
Page 10: ...www fanox com Rev 17 10 119 3 Phase CT and residual neutral Connection...
Page 34: ...www fanox com Rev 17 34 119...
Page 35: ...www fanox com Rev 17 35 119...
Page 36: ...www fanox com Rev 17 36 119...
Page 118: ...www fanox com Rev 17 118 119 NOTES...
Page 119: ...www fanox com Rev 17 119 119...