Rev. 07
19/138
4.
PROTECTION FUNCTIONS
4.1.
General settings
Additionally, it is necessary to define some previous parameters that will provide the SIA-C relay
information about what and how it is going to protect.
Group
Description
Minimum
Maximum
Step
Unit
Default
Generals
Identification
-
-
-
-
“free text”
Frequency
-
-
60/50
Hz
50
Serial Number
-
-
-
-
-
Language
0
3
1
-
ENGLISH
Active Settings Group (*)
1
4
1
-
1
Trip Voltage Level
12
24
12, 17, 22 or 24
Vdc
17
CT phase ratio
1.0
3000.0
0.1
-
1
CT neutral ratio
1.0
3000.0
0.1
-
1
Local Address
1
247
1
-
1
Remote address (*)
1
247
1
-
2
Remote baudrate (*)
4800
38400
4800, 9600, 19200 or 38400
-
19200
Remote Protocol (*)
-
-
Modbus RTU or DNP3.0
-
Modbus
(*) Optional depending on model
Next points must be considered referring general settings:
The serial number is only a reading setting.
The rest of the settings can be changed either from the HMI or through communications.
Any change of set values will restart all functions, irrespective they are activated or not.
Summary of Contents for SIA-B Series
Page 8: ...www fanox com Rev 07 8 138 Cut out pattern 2 3 Striker dimensions 2 3 1 PRT 15...
Page 9: ...www fanox com Rev 07 9 138 2 3 2 PRT A 44 5 B 49 5 C 56 5 D 64 5 E 42 5...
Page 10: ...www fanox com Rev 07 10 138 2 4 Connection diagram NOTE STRIKER 6 24 Vdc 0 135 W s...
Page 28: ...www fanox com Rev 07 28 138...
Page 35: ...www fanox com Rev 07 35 138...
Page 36: ...www fanox com Rev 07 36 138...
Page 37: ...www fanox com Rev 07 37 138...
Page 38: ...www fanox com Rev 07 38 138...
Page 40: ...www fanox com Rev 07 40 138...
Page 41: ...www fanox com Rev 07 41 138...
Page 42: ...www fanox com Rev 07 42 138...
Page 76: ...www fanox com Rev 07 76 138 6 3 Standards...
Page 77: ...www fanox com Rev 07 77 138...
Page 137: ...www fanox com Rev 07 137 138 NOTES...
Page 138: ...www fanox com Rev 07 138 138...