20
Rackmount Installation
Securing hardware, slide rails (SGRMKIT) and rail extensions (DP70357) are sold separately.
The UPS is designed to fit in a 19” equipment rack. Each UPS inverter and transformer module
requires 4U (7 inches / 178mm) of vertical rack space.
The supplied rack mounting ears are intended to secure the units to the rack rails. They do not
support the weight of the UPS, transformer or battery bank. Rack slides or shelves are required.
Reference the following procedure to install the UPS in a standard 19” equipment rack:
1.
Place the UPS on a flat, stable surface with either side of the UPS facing you.
2.
Align mounting ears with screw holes on each side of the UPS and secure with the supplied
screws. (12) M4 x 6mm.
a. Repeat the procedure for the transformer module or battery banks to be used.
(6) M4 x 6mm
Each Side