20
6.4 GAS SUPPLY & CONNECTION
6.4.1 Installation pipe work should be fitted in accordance with local / national standards.
The pipe work must not be smaller than unit gas inlet connection. If using flexible
hosing, the hose must be installed & sized to conform to BS 6173 and the length must
not exceed 1.5m. An isolating valve must be located close by for shut-down during an
emergency or servicing.
An inlet manifold is supplied with to enable connection to ¾”
BSP inlets.
6.4.2 If flexible hose is used, it shall comply with national requirements. These must be
periodically examined and replaced as necessary. A retention chain must also be
attached to the rear of the appliance.
6.4.3
Natural Gas Appliance
- Supplied governor must be fitted to the rear of the appliance.
(see section 8.9)
6.4.4 The installation should be checked for gas tightness and purged as specified in
IGE/UP/1.
6.5 ELECTRIC SUPPLY & CONNECTION
Not applicable to this appliance
Live 1 ( Phase 1)
Brown
Neutral
Blue
Earth
Yellow/Green
THIS APPLIANCE MUST BE EARTHED.