7. 

The pipes between the heat pump and pool should not be longer than 10 m, pipes longer than 10 m will 

reduce the efficiency of the heat pump.

8. 

Make sure that the on/off switch is out of the reach of children.

9. 

If the heat pump is to remain off for a long period of time, cut the power to the heat pump and drain it by 

closing the by-pass valves and disconnecting the water inlet pipe.

 

„

Maintenance

Disconnect the heat pump from its power supply before any intervention.

Winterizing :

 Drain the pump and disconnect it from its power supply. Cover it with a protective jacket.

Clean the outside of the pump using detergent and water. Never use organic solvants.

C

heck once a year at least  that the screws, bolts, cables and connections are correctly tightened.

Physico-chemical properties of pool  water:
The commonly available pool treatment chemicals are compatible with the materials used to build the heat pumps 

subject to the condition that the physico-chemical properties of the pool water fall within the following   ranges:

• 

pH between 7 and 7.4

• 

Total Hardness (TH) less than 200 ppm

• 

Cyanuric acid (stabiliser) concentration less than 80 ppm

• 

Free chlorine concentration: 1.0 to 1.5 ppm

• 

Free bromine concentration: 1.0 to 1.5 ppm

Check these properties at the beginning of the season before allowing water to circulate through the heat pump. Then 

recheck at regular intervals.

Caution:

«Shock»  Chlorination  of  the  pool:  before  super  chlorinating  the  pool  water,  stop  the  heat  pump  and  isolate  the 

hydraulic loop   (isolating valves) on which the heat pump is mounted. Do not reopen the valves until the chlorine 

concentration has fallen to normal levels.

 

„

Troubleshooting

Note:

 Should the circuit breaker trips frequently or the fuse blows  regularly, stop the machine immediately, cut the 

power supply and contact your dealer.

SYMPTOM

CAUSE

Steam escaping from the machine

The fan stops automatically for defrosting.

clicking/popping sound

The noise made by the 4-way valve during cycle inversions heating/defrosting  or defrosting/

heating.

Flowing sound

While the heat pump is running, or just after it stops, and during the first 2/3 minutes after the 
machine starts up. The noise can be caused by circulation of heat exchange fluid or drainage of 

condensates.

clicking/popping

The heat exchanger can make clicking/popping noises as it expands and contracts under the 
influence of temperature variations.

automatic start/ stop not functioning 
correctly

Power supply out of order.
Check that the manual on/off switch is set to on.
The circuit breaker has tripped/fuse has blown.

The machine is in delayed start phase (the on LED is lit up)
Timer on (the ‘On’ indicator light is lit up)

The machine does not start up

Check that the water temperature at the heat pump outlet is a few degrees warmer than the water 
temperature at the inlet. Check that the air inlet and exhaust are not  obstructed.

The machine is running but doesn't heat

Summary of Contents for PHC18L

Page 1: ...ion F Code 33436 FAIRLAND PIONEER Swimming POOL HEAT PUMPS PHC18L PHC25L PHC35L PHC50L PHC60L PHC60LS PHC80LS PHC120LS PHC150LS HORIZONTAL INSTALLATION AND OPERATING INSTRUCTIONS To be read carefully...

Page 2: ...s some useful advice Keep this document in a safe place and show it to any other user FOREWORD 15 OPERATING PRINCIPLE AND MAIN COMPONENTS 15 Compressor protection 16 TECHNICAL DATA 16 TECHNICAL SP CIF...

Page 3: ...t air which in turn is cooled down 2 the fluid enters the compressor here the fluid pressure is raised significantly thus further increasing its temperature 3 the fluid passes into the condenser heat...

Page 4: ...ge of 7 to 43 Their efficiency cannot be guaranteed outside this range Performance data and operating parameters can vary with changes in climatic conditions 2 The technical specifications are subject...

Page 5: ...chine with care never leave the machine lying on its side IMPORTANT never lift the machine by its hydraulic connections this would damage these connections with the heat exchanger located inside the m...

Page 6: ...rom its poser supply systematically prior to any technical intervention Should the cable be damaged it must be replaced by the manufacturer its after sales service or other similarly qualified personn...

Page 7: ...s of the heat pump see the Siting paragraph page 24 so that operation of the pump is not impeded or even stopped 4 The heat pump needs an additional pump to drive circulation of the pool water pool fi...

Page 8: ...t the installation configuration will not allow accidental siphoning from the treatment chemical tanks while filtration is not running Be careful not to allow impurities stones earth etc to enter the...

Page 9: ...ing before you start up the heat pump 7 With the filtration pump running check for leaks set the temperature set point and start up the heat pump 8 When the heat pump starts up the fan switches on imm...

Page 10: ...pump Then recheck at regular intervals Caution Shock Chlorination of the pool before super chlorinating the pool water stop the heat pump and isolate the hydraulic loop isolating valves on which the h...

Page 11: ...e a precise description of the damage noted on the transporter s delivery slip and send a letter of complaint by registered mail with acknowl edgement of receipt to the transporter within 3 working da...

Page 12: ...24 36 2015 12 Indice de r vision F Code 33436 NOTES...

Page 13: ...e 33436 FAIRLAND PIONEER W RME PUMPEN F R SCHWIMM B DER PH18L PH25L PH35L PH50L PH60L PH60LS PH80LS PH120LS PH150LS HORIZONTAL MONTAGE UND BEDIENUNGSANlEITUNG Bitte lesen sie sich diese anleitung sorg...

Page 14: ...nach der Installation an einem sicheren Platz und stellen Sie sicher dass sie von allen Nutzern gelesen wird VEREHRTE KUNDEN 27 FUNKTIONSPRINZIP UND HAUPTBESTANDTEILE 27 Schutz des Kompressors 28 TECH...

Page 15: ...e en ber den Lamellenverdampfer Der Ventilator bewegt die Luft ber die Aluminiumlamellen welche die Kupferleitungen bedecken durch die der W rmetr ger flie t Der W rmetr ger erw rmt sich und die Umgeb...

Page 16: ...Sie dabei dass nach 3 x 6 mm der n chst h here Kabelquerschnitt 3 x 10 mm betr gt 3 Das Kabel des fern installierten Steuerkastens darf nicht l nger als 50 m sein 3 x 0 5 mm2 4 Werte g ltig unter fol...

Page 17: ...b ist k nnen einige Teile des K ltemittelkreislaufs sehr hei andere dagegen sehr kalt werden Ein ffnen des Ger ts um dadurch Zugang zu diesen Teilen zu erlangen ist ausschlie lich qualifizierten Fachk...

Page 18: ...Schutzschalter 30mA geschutzt ist Ist dies nicht der Fall mussen sie auserhalb der drei Bereiche aufgestellt werden Die aktiven Pole m ssen von der Stromquelle getrennt werden k nnen Sollte das Kabel...

Page 19: ...en Sie f r ordnungsgem en Abfluss des Kondensats An merkung Ein Entweichen von Kondensat am Fu e der W rmepumpe ist ein Zeichen f r deren korrekten Betrieb es weist nicht auf ein Leck im K ltemittelkr...

Page 20: ...sanschluss der W rmepumpe einem Kugelhahn am Ausgangsanschluss der W rmepumpe Die beiden letztgenannten Kugelh hne sind normalerweise offen und sollten nur dann geschlossen werden wenn es Wartungsarbe...

Page 21: ...ezeigt Einstellen des Wassertemperatur Sollwerts 1 Diese Schritte k nnen bei ein oder ausgeschalteter W rmepumpe durchgef hrt werden 2 Dr cken Sie die Pfeiltasten oder um den Temperatur Sollwert einzu...

Page 22: ...e W rmepumpe sofort ab und setzen Sie sich mit Ihrem Fachh ndler in Verbindung Versuchen Sie nie die W rmepumpe selbst zu reparieren 5 Leicht entflammbare Materialien d rfen in unmittelbarer N he der...

Page 23: ...ig aktiviert oder die Sicherung springt regelm ig heraus SYMPTOM URSACHE Aus dem Ger t entweicht Dampf Der Ventilator h lt zum Abtauen automatisch an klopfger usche Das Ger usch des 4 Wege Ventils be...

Page 24: ...eckt verantwortlich Sie als Kunde sind verpflichtet die gelieferte Ware unverz glich auf M ngel zu berpr fen und etwaige Beanstandungen m glichst genau auf dem Transportschein zu vermerken Schicken Si...

Page 25: ...E Page 13 Page 25 POMPE A CHALEUR FAIRLAND PIONEER POUR PISCINES PHC18L PHC25L PHC35L PHC50L PHC60L PHC60LS PHC80LS PHC120LS PHC150LS HORIZONTALES NOTICE D INSTALLATION ET CONSEILS D UTILISATION lire...

Page 26: ...3 Raccordement lectrique Machine monophas e 9 UTILISATION 9 Temp rature de consigne de l eau de la piscine 9 V RIFICATION AVANT PREMI RE UTILISATION 10 PR CAUTIONS 10 ENTRETIEN 10 PANNES ET ANOMALIES...

Page 27: ...t Un fluide caloporteur R 410 A tourne en boucle dans un circuit au cours duquel il est soumis aux tapes du cycle suivant 1 r cup ration des calories de l air ambiant au passage dans l vaporateur aile...

Page 28: ...le pour une longueur inf rieure 10 m est 3 x 2 5 mm pour une longueur sup rieure 10 m il convient d utiliser de 3 x 4 mm A noter que la section sup rieure au 3 x 6 mm est 3 x 10 mm 3 Le cordon du bo t...

Page 29: ...plaque signal tique sur la pompe chaleur pour plus d informations Dimensions en mm Ces donn es sont sujettes modification sans notification Note Les dimensions ci dessus sont destination de l install...

Page 30: ...prot ger specifiquement leur ligne d alimentation par un differentiel 30mA A defaut elles doivent imperativement etre placees en dehors des 3 volumes Un moyen de d connexion de tous les p les actifs...

Page 31: ...s la pompe chaleur doit tre ais afin de faciliter les op rations de maintenance qui peuvent n cessiter de transporter du mat riel lourd L eau ne doit pas s accumuler au pied de la machine en cas de p...

Page 32: ...e retour celle ci permet de r gler le ratio entre le flux d eau traversant la P A C et le flux d eau ne la traversant pas de fa on obtenir le d bit pr conis travers la P A C cf tableau de sp cificatio...

Page 33: ...la valeur de la consigne exercer une pression rapide sur les fl ches ou la valeur de la consigne appara t et l affichage revient la normale apr s 5 secondes 2 Pour modifier la valeur de la consigne e...

Page 34: ...optimiser l effet chauffage assurez vous que les tuyaux entre la pompe chaleur et la piscine sont thermiquement isol s Pendant la p riode d utilisation il est recommand en dehors du temps de baignade...

Page 35: ...ffage Bruit d coulement Pendant le fonctionnement ou juste apr s l arr t le bruit d coulement d eau et pendant les premi res 2 3 minutes apr s que la machine est mise en marche Le bruit correspond l c...

Page 36: ...12 36 2015 12 Indice de r vision F Code 33436 NOTES...

Reviews: