16
Rated operational voltages
U
e
200Vac to 480Vac
Rated operational current
I
e
See Rating table
Rating index
SGY-401 to SGY-505
Ie: AC-53a: 3.5-17: 60-3
Rated frequency
50 to 60Hz
Rated duty
Uninterrupted
Form designation
Form 1
Rated insulation voltage
U
i
480V
Rated impulse withstand
voltage
U
imp
Main circuit
4kV
Control supply circuit
2.5kV
IP code
Main circuit
IP00
Supply and control circuit
IP 20
Pollution degree
2
Rated conditional short-circuit current and type
of co-ordination with associated short circuit
protective device (SCPD).
Type 1 co-ordination. See short circuit protection table
for rated conditional short-circuit current and required
current rating and characteristics of the associated
SCPD
Rated control circuit voltage
(programmable)
U
c
24Vdc, 110Vac or 230Vac
Protect with 4A UL Listed
fuse
Rated control supply voltage
U
s
See Rating table, 2 Amp
supply (continuous).
Relay specification
AC-15 230Vac, 1A
DC-13 30Vdc, 0.7A
EMC Emission levels
EN 55011
Class A
u
EMC Immunity levels
IEC 61000-4-2
8kV/air discharge or 4kV/contact discharge
IEC 61000-4-3
10 V/m
IEC 61000-4-4
2kV/5kHz (main power and ports)
1kV/5kHz (signal ports)
IEC 61000-4-5
2kV line-to-ground
1kV line-to-line
IEC 61000-4-6
10V
Humidity
Max. 85% non-condensing, not exceeding 50% at 40°C
Technical information/Standards
NOTICE: This product has been designed for environment A. Use of this product in environment
B may cause unwanted electromagnetic disturbances, in which case the user may be required to
take adequate mitigation measures.