15
Type
IEC, Ie
A
3)
kW
1)
UL, FLA
A
4)
HP
2)
Control
supply
U
s
230V
400V
200V
208V
220-
240V
440-
480V
SGY-401-4-XX
610
200
355
590
200
200
200
500
24Vdc
or
110Vac
or
230Vac
SGY-403-4-XX
722
220
400
722
250
250
300
600
SGY-501-4-XX
850
280
500
840
300
300
350
700
SGY-503-4-XX
960
315
560
960
300
350
400
800
SGY-505-4-XX
1080
355
630
1080
350
400
450
900
Rating table
1) Rated operational powers in kW according to IEC 60072-1 (primary series) corresponding to
IEC current rating.
2) Rated operational powers in HP ased on Table 430.250 of the National Electrical Code,
2005® corresponding to FLA current rating.
3) The IEC, Ie rating will apply for EN 60947-4-2 max rating index 1080A: AC-53a: 3.5-17: 60-3
4) Ratings apply for a maximum surrounding air temperature of 40°C.
1
10
100
1000
1
1.5
2
2.5
3
3.5
4
4.5
Trip time ( seconds )
Multiple of Motor FLA
Motor overload 'cold' trip curves
(20°C ambient)
Class10
Class20
Class30
* Please note: When the overload has tripped there is a forced cooling
time to allow the overload to recover before the next start.