39
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Modbus RTU Serial Communications
Modbus RTU Communications Interface
All agility
TM
soft starts support Modbus RTU as standard. The RS-485 communications are accessible from
the RJ45 connector (see below).
1:
Not connected
2: Not connected
3: Not connected
4: TXD1-B-OUT
5: TXD0-A-OUT
6: Reserved*
7: Reserved*
8: GND
*
Warning: To avoid
damage to the unit
or to the RS-485
master, do NOT
connect to these
pins!
Modbus RTU Connections
Single agility
TM
RS-485 network
Multiple agility
TM
RS-485 network
RJ45 Socket
Communication
CBL-036
CBL-035 Terminator
(last unit only)
PLC (Master)
PLC (Master)
The agility
TM
units must have: a unique Modbus address on each unit
and identical Parity/Baud rate values on each unit