31
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
Modbus Enable
Enable using Modbus
On: The unit is enabled
Off: The unit is disabled
Modbus Reset
Reset using Modbus
On: The initial state required for a reset.
Off: The final state required for a reset.
To reset pulse high and then low
Modbus Start
Start / Stop using Modbus
On: Starts the unit
Off: Stops or Soft stops the unit
Model No
The device Model number stored at the point of manufacture
Motor Amps
This should be set to the Full Load Current shown on the motor plate
The overload works with multiples of the set "Motor Amps"
Also referred to as Motor FLA
MotorState
Indicates the unit operating State
Op Mode
Overheat
Detects if the internal temperature sensor has malfunctioned
Trip On: The unit will trip if the internal temperature sensor
malfunctions
Trip Off: The unit will continue to operate even if the temperature sensor
has malfunctioned.
Operating with the Trip Off for prolonged periods may result in SCR
failure
Overload
The unit has an "Overload" function that is an electronic
equivalent to a thermal overload.
Overload displays the overload capacity which is a measure of how close
the unit to tripping on "Overload Trip"
When "Irms" is greater than the "Overload Amps" the "Overload"
increases in accordance with the "Trip Class".
When "Current Irms" is less than "Overload Level" the "Overload"
decreases exponentially (if greater than 50%)
When the "Overload" reaches 100% the unit will trip.
During situations when "Motor Amps" is equal to "unit Amps" the
overload will indicate 50%