Page 13/37
SEPARIX-C/-T and SEPARIX-Control CT
A system test is only possible if the SEPARIX-T L Plus high-level sensor
has been heated up.
If the test button is pressed alone, an unacknowledged alarm will be sim-
ulated. If both the test and acknowledge buttons are pressed
simultaneously, an acknowledged alarm will be simulated.
The test button does not replace the function test of the warning system
(see section 5).
The measuring transducer configuration settings allow both buttons to be locked, e.g. in
cases where the measuring transducer is part of a central control system and the system
operator shall not acknowledge any faults or carry out any tests (see section 4.2).
4.2
Configuration
The measuring transducer is factory preconfigured and ready for operation. With the help
of the "Options" DIP switch you are able to configure SEPARIX-Control CT (see following
table):
Option
DIP switch OFF
DIP switch ON
1
SEPARIX-C …
OFF
ON *
2
SEPARIX-T …
OFF
ON *
3
Relay energised
Alarm *
No alarm
4
Relay acknowledgeable
Yes *
No
5
Alarm delay
60 sec. *
No
6
Acknowledge button
Locked
Unlocked *
7
Test button
Locked
Unlocked *
8
Alarm buzzer
Locked
Unlocked *
* : Default factory setting
Table 1: SEPARIX-Control CT, configuration
Summary of Contents for SEPARIX-C L Plus
Page 25: ......
Page 26: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 41: ...Blank Page...
Page 42: ...Blank Page...
Page 43: ...Blank Page...