Elpro S40
!
!
IP 66
ELECTRIC CONNECTIONS TO THE ELECTRONIC CONTROLLER ELPRO S40
The electronic controller Elpro S40 is to be installed in a dry and protected place to prevent unauthorized actions.
Make sure that all the electric cables of the command and safety accessories are properly led to the controller (Pic.3).
Through the previously laid corrugated tube pull a multicore cable, type
BUT FLESSIBILE FG 7OR 12x1,5 mm²
(not supplied
with the equipment, but available on request as per catalogue) or a multicore cable, type
BUT FLESSIBILE FG 7OR 16x1,5 mm²
(not supplied with the equipment, but available on request as per catalogue) for the electrical connections to the Elpro S40
controller, depending on which model of TALOS is required to be installed (see page 18, point 8).
NOTE WELL: Lay a ground cable suitable to the type of installation as required either for public or private users and in
compliance with the existing safety norms. A screw is provided for proper connection.
For applications in public areas use a cable having a section of 16 mm
².
Multicore cable
and ground cable
Pic. 12
The multipole cable BUT FLESSIBILE FG 7OR 12x1,5 mm² or BUT FLESSIBILE FG 7OR 16x1,5 mm²
(see page 18, point 8) is required to have a maximum length of 50 m.
The ground cable must have a section complying with the installation requirements.
ATTENTION: before carrying on with wiring, it is recommended to identify which optional accessories TALOS
is actually fitted with (pressure switch, solenoid valve, beeper or heating resistor), so to arrange the proper
connections to the respective terminals in the connector.
Hydraulic
motor-pump
Pressure switch
Beeper
Heating resistor
Solenoid valve
Beeper
inside
the post
Heating resistor
inside
the casing
Pic. 13
Retractable Oil-hydraulic Bollard
English
Pressure switch
or presence
detector
Solenoid valve
Hydraulic
motor-pump
10