Elpro 42

GB

12

Dip-Switches 

   1 = 

OFF

 Photocell. No stop in opening

   2 = 

OFF 

Radio contact 3-7 stop and reverse in opening

   3 = 

OFF

 Semiautomatic functioning

   4 = 

OFF

 No pre-flashing before opening

   5 = 

OFF 

Radio contact 3-7 reverse on each pulsing

   6 = 

OFF

   7 = 

OFF 

No stroke reversing pulse in opening. 

   8 = 

OFF 

Flasher (contact 11-12) ON in dwell time. 

   9 = 

OFF 

No reclosing after crossing the photocells

10 = 

OFF

 No photocell DSA control before any operation

11 = 

OFF

 Blank

12 = 

OFF 

Blank

 

   1 = 

ON

 Photocell. Stop in opening

   2 = 

ON 

Radio contact 3-7 no stop and no reverse in opening

   3 = 

ON

 Automatic closing after dwell time

   4 = 

ON

 Fixed pre-flasing before gate moving

   5 = 

ON 

Radio contact 3-7 step by step: open-stop-close-stop

   6 = 

ON 

Enable braking speed adjustment

   7 = 

ON 

Stroke reversing pulse for 2 s is enabled in opening

   8 = 

ON 

Flasher (contact 11-12) OFF in dwell time. 

   9 = 

ON 

Reclosing after crossing the photocells (

 Dip 3= ON

)

10 = 

ON

 Photocell DSA control before any operation

11 = 

ON

 Blank

12 = 

ON 

Blank

ON

OFF

123

4

5

6

7

8

9
1

0
1

1
1

2

DIP

-SWIT

CH  

NOTE WELL:  THE INSTALLATION OF NON FADINI ORIGINAL ACCESSORIES MAY DAMAGE THE PC BOARD. MAKE  
SURE THAT FREE CONTACTS BE ALWAYS USED FOR THE NO-NC INPUTS. BRIDGE ALL THE NC CONTACTS NOT IN USE.

!

!

common

common

open

close

st

op

+

+

ON

: stop in opening and reverse in closing once

 obstacle is removed

OFF

: no stop in opening and reverse in closing

when obstructed 

ON

: no stop and no reverse in opening

OFF

: stop and reverse in opening on pulsing

L7 red OFF

 = no RADIO contact,

it goes ON whenever a radio pulse is given

ON

: step by step with stop in between

OFF

: gate travel reverse on radio pulsing

L2 green ON 

= no obstacle detected,

goes OFF when an obstacle is detected

L4 red OFF

 = no OPEN contact,

it goes ON whenever an open pulse is given

L5 red OFF

 = no CLOSE contact,

it goes ON whenever a close pulse is given

L6 green ON

 = STOP contact closed,

it goes OFF whenever a stop pulse is given

By any NO connection to these two terminals 
the following is performed, on each pulsing:

- Opening only: 

Dip 2=ON and Dip 5=OFF

- Travel reversing  on each pulsing

Dip 2=OFF and Dip 5=OFF

- Step by step operations: 
open-stop-close-stop

Dip 2=OFF and Dip 5=ON

DIP-SWITCH N° 1:

DIP-SWITCHES N° 2 AND 5 (do NOT set both of 
them to ON at the same time):

2

5

1

Radio contact:

Keyswitch:

Photocells:

RADIO

CONTACT

inner

NC

NC

NC

NC

NC

outer

+

Accessory

Electrical connections

Dip-switch and LED indication

of the various functions

View from inside property:

Outer photocells:

all the 

NC contacts

 of the receivers of the outer 

photocells are to be 

series

 connected to 

terminals 

1

 and 

2

: on being engaged, in closing 

phase,  gate travel is revered to open.

Inner photocells:

all the 

NC contacts

 of the receivers of the inner 

photocells are to be 

series

 connected: on being 

engaged, gate travel is stopped in opening, 
closing and dwell time untill cleared. 

NO and NC contacts to be connected to the 
respective terminals of the key- or 
button-operated switches. 
All possible configurations are in the 
instructions attached to the specific 
command accessory.

F

3    4    5    6

3

-

Output provided in case a light be required to indicate
gate status:
Light 

ON

 = gate open

Light 

OFF

 = gate closed

Flashing  

0,5 s (fast)

 = gate closing

Flashing 

1 s (normal)

 = gate opening

24 V - max 3 W
pilot light
output:

+

8 9

7

F 1 2

Main PCB

ZERO.DGT

Receiver

ZERO.SAPE

ZERO.EK

ZERO.K

ZERO.PH Trifo 11

Orbita 57

Receivers:
Astro 43, 
Jubi 433,
Siti 63, Birio 868, VIX 53

ELECTRONIC CONTROLLER FOR DARDO 424 AND FOX 724 

GATE OPERATOR ON DOUBLE SWINGING GATES

SELECT VIA DIP-SWITCH N.1 WHETHER TO USE DART 424 OR FOX 724. All possible connections to the programmer 
terminals are also illustrated in the instruction sheets of the individual accessories.

Summary of Contents for DARDO 424 e FOX 724

Page 1: ...PAS PAS SORTIES POUR N 2 MOTEURS MASTER SLAVE PROGRAMMATION AUTOMATIQUE AVEC OU SANS RETARDS VANTAIL RALENTISSEMENT FIXE A L OUVERTURE ET A LA FERMETURE FONCTION AMPEROMETRIQUE POUR INVERSION DE MARC...

Page 2: ...uire una attenta analisi dei rischi utilizzando appositi strumenti di rilevazione di impatto e schiacciamento del bordo principale di apertura e chiusura secondo quanto indicato nella normativa EN 124...

Page 3: ...Rosso spento Si illumina ad ogni comando pedonale E1 Rosso acceso Led encoder E2 Rosso acceso Led encoder Descrizione generale il programmatore elettronico ELPRO 42 stato realizzato per gestire l apr...

Page 4: ...rmedio OFF inverte il movimento ad ogni impulso radio L2 verde Acceso nessun ostacolo presente si spegne al rilevamento dell ostacolo L4 rosso spento nessun contatto APRE si accende ad ogni impulso di...

Page 5: ...della costa di sicurezza L16 verde acceso costa di sicurezza in chiusura si spegne ad ogni intervento della costa di sicurezza M1 comune In serie se coste meccaniche NC comune NC NC In serie se coste...

Page 6: ...a velocit massima durante la corsa La nuova velocit verr eseguita al successivo comando apre chiude radio Alimentazione quadro 230 V 50 Hz Uscita alimentazione M1 Uscita alimentazione M2 M1 Dardo sull...

Page 7: ...ase di chiusura la funzione inverte la marcia fino alla battuta di apertura N B Se per 5 volte consecutive rileva un ostacolo durante un ciclo completo di apre pausa chiude il cancello rimane aperto i...

Page 8: ...ontatto di stop coste di sicurezza PROGRAMMAZIONE SENZA RITARDO DELLE ANTE quando le due ante del cancello si aprono contemporaneamente e per installazioni con un solo motoriduttore su cancelli ad una...

Page 9: ...rogrammazione Premere e tenere premuto per 5 secondi il pulsante di programmazione fino a che il led LP non inizia a lampeggiare si entra cos in programmazione M2 M2 Dare un singolo impulso il led LP...

Page 10: ...rce of the main opening and closing edge in compliance with EN 12445 Identify the appropriate solution necessary to eliminate and reduce such risks In case where the gate to automate is equipped with...

Page 11: ...itches OFF whenever the safety edge is engaged L16 Green ON Safety edge close switches OFF whenever the safety edge is engaged L18 Red OFF Switches ON whenever a pedestrian command is given E1 Red ON...

Page 12: ...given L5 red OFF no CLOSE contact it goes ON whenever a close pulse is given L6 green ON STOP contact closed it goes OFF whenever a stop pulse is given By any NO connection to these two terminals the...

Page 13: ...y edge is activated L16 green ON safety edge in closing It goes OFF whenever the safety edge is activated M1 common In series if NC mechanical type common NC NC In series if NC mechanical type In para...

Page 14: ...r supply 230 V 50 Hz Power supply output M1 Power supply output M2 M1 Dardo Fox on the 1st gate leaf to open and being also the pedestrian one if required M2 Dardo Fox on the gate leaf delayed on open...

Page 15: ...o the gate stop in open position N W In case an obstacle is detected for 5 consecutive times during a complete cycle open dwell close the gate stays open waiting for a command Dwell trimmer dwell time...

Page 16: ...for single gate applications where one motor only is involved Once all the electrical connections to the control unit have been properly made following the instructions included in the box with all o...

Page 17: ...on for 5 seconds until the LP led starts flashing programming mode is thus accessed M2 M2 Pulse just once the LP led light is steady on Within 10 seconds from the previous pulse give a second pulse pr...

Page 18: ...photocellules d tecteurs des masses m talliques listeaux sensibles etc Effectuer une analyse des risques en utilisant instruments de d tection de l impact et crasement du bord principale d ouverture e...

Page 19: ...eau de s curit L16 Verte allum e Listeau de s curit la fermeture s teint chaque intervention du listeau de s curit L18 Rouge teinte S allume chaque commande pi tons E1 Rouge allum e LED encodeur E2 Ro...

Page 20: ...t inverse toujours L7 rouge teinte aucun contact RADIO s allume chaque impulsion du contact radio ON pas pas avec arr t interm diaire OFF inverse le mouvement chaque impulsion radio L2 verte Allum e a...

Page 21: ...mun NF NF commun L15 verte allum e listeau de s curit l ouverture elle s teint chaque intervention du listeau de s curit L16 verte allum e listeau de s curit la fermeture elle s teint chaque intervent...

Page 22: ...ant la course La nouvelle vitesse sera r alis e la commande ouvre ferme radio qui suit Alimentation panneau 230 V 50 Hz Sortie alimentation M1 Sortie alimentation M2 M1 Dardo Fox sur le 1er vantail l...

Page 23: ...ion inverse la marche jusqu la but e d ouverture N B Si pour 5 fois cons cutives le portail d tecte un obstacle pendant le cycle complet ouvre arr t ferme le portail reste ouvert dans l attente d une...

Page 24: ...n possible accouplage de la serrure lectrique 1 2 3 6 ON j active le r glage de la vitesse en phase de ralentissement DIP SWITCH N 6 Trimmer vitesse 20 vitesse maximale 70 vitesse maximale 50 vitesse...

Page 25: ...vous entrez en modalit programmation Donnez seulement une impulsion la LED LP reste allum e fixe Dans les 10 secondes partir de l impulsion pr c dente donnez une seconde impulsion vous entrez dans la...

Page 26: ...der Gegenwart in der N he von Sicherheitseinrichtungen wie Lichtschranken Sicherheitsleisten etc F hren Sie eine sorgf ltige Risikoanalyse unter Verwendung geeigneter Instrumenten zur Erkennung von S...

Page 27: ...lie ung es schaltet sich aus wenn die Schaltleiste engagiert ist L18 rot AUS Es schaltet sich bei jeder Geht r Impulsgabe ein E1 rot AN LED Encoder E2 rot AN LED Encoder Allgemeine Beschreibung Die el...

Page 28: ...et sich bei jedem Funk Impuls ein ON Schritt f r Schritt mit Zwischenstopp OFF Umkehr bei jedem Funkimpuls L2gr n AN Kein Hindernis erkannt es geht aus falls ein Hindernis eintritt L4 rot AUS kein AUF...

Page 29: ...sich aus wenn die Leiste engagiert ist M1 Common In Serie im Fall von NC mechanische Schaltleisten Common NC NC In Serie im Fall von NC mechanische Schaltleisten Parallel im Fall von Resistiven 8 2 k...

Page 30: ...V 50 Hz M1 Stromversorgung Ausgang M2 Stromversorgung Ausgang M1 Dardo Fox auf dem ersten ffnenden Torfl gel und wobei auf der Fu g nger Torfl gel falls erforderlich M2 Dardo Fox auf dem Torfl gel ve...

Page 31: ...on umgekehrt NB Wenn ein Hindernis f r 5 aufeinanderfolgende Male w hrend eines kompletten Zyklus Open Pause Close erkannt wird bleibt das Tor offen und wartet auf einen Befehl Pause Trimmer Die Pause...

Page 32: ...schl sse an das Steuerger t ordnungsgem ausgef hrt wurden nach den im Lieferumfang enthaltenen Anleitungen mit allen Sicherheits und Befehlszubeh r je nach Bedarf k nnen Sie die Programmierung durchf...

Page 33: ...egriffen M2 M2 Geben Sie einen Impuls nur einmal das LP LED Licht bleibt AN Innerhalb von 10 Sekunden nach dem vorherigen Impuls geben Sie einen zweiten Impuls Programmiermodus mit Torfl gelverz gerun...

Page 34: ...Elpro 42 34...

Page 35: ...Elpro 42 35...

Page 36: ...max moteurs 200 W Sortie lumi re de courtoisie 24 Vdc 50 mA Sortiephotocellules s lecteur r cepteurradio 24 Vdc 500 mA Sortie voyant de signalisation 24 Vdc 3 W Sortie pour contr le DSA 24 Vdc 150 mA...

Reviews: