19
Close Time Delay Adjustment
The gate operator is equipped with a built-in automatic timer to close feature. This feature should be set to the OFF position un-
til proper safety and reverse devices have been installed.
CAUTION
: Turning on the Close Time Delay without proper safety and
reverse devices can cause serious injury, death, and property damage. The Close Time Delay can be set to from 1 to 90 seconds.
When active, the Close Time Delay will hold the gate open until the internal timer has timed out and then allows the gate to close.
Switch
Function
Description
1
Monitor Photo /
Edge
OFF: The Photo safety inputs are monitored
ON: The Edge safety inputs are monitored
2
Anti-Tailgate
OFF: Gate opens and closes normally. Reverse loop reverses the gate all the way
ON: Uses loops to control vehicles individually. Reverse loop stops the gate
3
Master / Slave
OFF: Operator is set as a Master
ON: Operator is set as a Slave
4
Close Timer
OFF: Time Delay Close feature is inactive. Command to open, command to close.
ON: Time Delay Close feature is active. Gate opens, times out, closes.
5
Power Fail Cycle
/ Open
OFF: During power failure, gate will cycle using BBU until batteries are too low to function.
ON: During power failure, gate will open and remain open until AC power is restored.
6
Open Left / Right OFF: Opens the gate Left. (Standing inside looking out at operator)
ON: Opens the gate Right. (Standing inside looking out at operator)
7
Quick Close
OFF: Gate opens and closes normal
ON: Gate opens until loops reverse and shadow loops are cleared. Then gate closes even if
it did not reach full open position
8
Stop (NO / NC)
OFF: Allows a NO Stop Switch to be used.
ON: Allows a NC Stop Switch to be used. Stop Switch must be installed for this setting to be ON
9
Battery Cycle
OFF: Cycles gate until batteries are too low and stops. Switch 5 must be OFF
ON: Cycles gate until batteries are too low and then opens gate. Switch 5 must be OFF
10
Mag / Solenoid
Delay
OFF: No delay - opens gate immediately
ON: Delays 2 seconds before activating gate. Allows time for Maglock to discharge
11
Monitor Close /
Op-Cl
OFF: The Close safety inputs only are monitored
ON: The Close and Open safety inputs are monitored
12
Hard Start
OFF: Normal Soft Start, Soft Stop mode.
ON: Operator starts with 40% motor power for more starting torque. Normal start = 5% motor
power
Timer ON
To turn OFF/ON and adjust the Close Time Delay:
1. To turn OFF the Close Time Delay, move DIP SWITCH 4 to the Left.
2. To turn ON the Close Time Delay, move DIP SWITCH 4 to the Right.
3.
Turn power Off and back On to reset DIP Switch settings.
4. Rotate the TIME DELAY adjustment clockwise to INCREASE the delay.
5. Rotate the TIME DELAY adjustment counter-clockwise to DECREASE the delay.
Monitor Photo / Edge
Anti-Tailgate
Master / Slave
Close Timer
Power Fail Open / Cycle
Open Left / Right
Quick Close
Stop (NC / NO)
Low Battery Cycle / Open
Mag / Solenoid Delay
Monitor Close / Op-Cl
Soft Start / Hard Start
Off On
DIP SWITCH 4
Clockwise Turn
INCREASE
Time Delay
(Holds gate open longer time)
Counter-Clockwise Turn
DECREASE
Time Delay
(Holds gate open shorter time)
DIP Switch Settings
The DIP Switches located on the top right face of the controller are used to set several different functions. This list gives a brief
description. Please review each individual section in this manual for more detail.
CAUTION
: Gently rotate each adjustment.
Turning the adjustment POT too hard will
break the adjustment.
Time Delay
Open Sensitivity
Close Sensitivity
+
+
+
Summary of Contents for FSL700