EP
SEMI-AUTOMATIC STEP-BY-STEP
This logic only requires the OPEN command to be used.
OPEN if the automation is closed, causes it to open.
OPEN if the automation is open, causes it to close.
OPEN during opening or closing, stops it and the
next OPEN command reverses the direction.
■
C
HOLD-TO-RUN
This logic requires the maintained OPEN A (open) and
OPEN B (close) commands to be used.
!
In the hold-to-run mode:
- the control must be activated intentionally and the
gate must be visible
- the SAFE inputs stop the movement immediately
Maintained OPEN A opens the automation.
Maintained OPEN B closes the automation.
■
b
SEMI-AUTOMATIC b
This logic requires the OPEN A (open) and OPEN B
(close) commands to be used.
OPEN A if the automation is closed, causes it to open.
OPEN A during opening, has no effect.
OPEN A during closing, causes it to reopen.
OPEN B if the automation is open, causes it to close.
OPEN B during closing, has no effect.
OPEN B during opening, causes it to close.
Movement stops if the closing photocells are triggered.
6.3 SETUP
The SETUP must be carried out when the board is first
installed, each time the board is replaced or installed
in another system, or if the characteristics of the gate
change.
Set-up procedure:
-
The gate MUST engage the CLOSED limit switch
(make sure that the FCC LED is off).
-
Select the
tl
function in programming.
-
Press and hold down the + and - buttons simul-
taneously, the gate starts to open and
S1
appears
on the display.
-
SETUP is complete when the open limit switch is
reached.
6.4 RESTORE THE DEFAULT VALUES
To restore the default values for all the functions:
-
Press and hold down the
+
,
-
,
F
buttons simultane-
ously for 10 seconds
-
Release the buttons when the separator point
between the two digits on the display flashes
7. PUTTING INTO SERVICE
7.1 FINAL CHECKS
1. Make sure that the forces generated by the gate
are within the limits permitted by the current
regulations. Use an impact force tester in ac-
cordance with EN 12453. For non-EU countries,
of there are no specific local regulations, the force
must be less than 150 N. If necessary, make any
adjustments that may be needed by referring also
to the gearmotor instructions.
2. Carry out a complete functional test of the automa-
tion and all the installed devices.
3. Refer to the gearmotor instructions for any ad-
ditional tests that may be required.
7.2 CLOSE THE ENCLOSURE
Close the enclosure in which the board is housed by
referring to the specific instructions.
7.3 FINAL OPERATIONS
Make sure that the system delivery requirements
have been fulfilled (otherwise arrange for them) i.e.
that they correspond to the board installed / replaced.