background image

15

ENGLISH

8  TESTING THE AUTOMATED SYSTEM

After installation and programming, check the system is 
operating correctly. Above all, check that the safety de-
vices operate correctly and ensure that the current safety 
regulations are met.

9  ALARM AND ERROR SIGNALS

If 

alarms

 occur (conditions that do not impair the opera-

tion of the gate) or 

errors

 (conditions that lock the gate 

operation) the display shows a number relating to the 
current condition.

 The ALARM or ERROR signals disappear at 

the next cycle only if the triggering cause 

is removed.

7.3  SETUP

 

 When the board is powered when no SETUP 

has ever been carried out, or if the board 

requires it, the code 

S0

 will flash on the 

display together with the SETUP led to indi-

cate that SETUP must be carried out.

 To ensure the effective outcome of the 

SETUP procedure, carefully check the cor-

rect polarity of the magnetic limit switches 

as described in the previous paragraph.

Proceed as follows to carry out the SETUP:

Move the gate leaf to mid-way through its travel (very 
important to the success of the SETUP) and check 
that both leds FCA and FCC are on. Otherwise, the 
board will indicate error 12 (see tab. 5)

Press and  hold the SETUP (SW4) push-button until the 
gate begins to move slowly and stops when it reaches 
the limit switch. If the limit switch reached is the closing 
switch (with the 

SQUARE

) the device stores that point 

as the 

closing

 stop, conversely if the limit switch is the 

opening switch (with the 

CIRCLE

) the device stores 

that point as the 

opening

 stop. During that stage, 

S 1

 

flashes on the display
The gate automatically begins to move slowly in the 
opposite direction and then stops when it reaches the 
limit switch. If the limit switch reached is the opening 
switch (with the 

SQUARE

) the device stores that point 

as the 

opening

 stop, conversely if the limit switch is 

the closing switch (with the 

SQUARE

) the device stores 

that point as the 

closing

 stop. During that stage, 

S 3

 flashes on the display

According to the final limit switch reached, the de-
vice takes up a status of closed (

0 0

) or open (

0 1

). 

In the second case, issue an OPEN pulse to close the 
gate.

1.

2.

3.

4.

9.1  ALARMS

 

 When an ALARM occurs, the ERROR led 

begins to flash and a number relating to 

the current fault appears on the display 

when the + and - keys are pressed.

Tab. 4 indicates all the alarms that may be shown on the 

display.

Tab. 4 - Alarms

2 2

Limited MOTOR current

2 4

LAMP output short-circuited

2 7

Obstacle detection (visible for 10 secs)

3 0

XF radio code memory-module full  (visible 
for 10 secs)

4 0

Service request

4 6

Forced default programming reset

9.2  ERRORS 

 When an ERROR occurs, led DL20 comes 

on with a fixed light and a number relating 

to the current fault appears on the display 

when the + and - keys  are pressed.

Tab. 5 indicates all the errors that may be shown on the 

display.

Tab. 5 - Errors

0 1

Board faulty

0 3

Motor faulty

0 6

Motor lock locked closed (check the motor 
lock and replace if necessary)

0 7

Gate too heavy or too much friction (try to 
increase motor power)

0 8

BUS-2EASY device error  (e.g. same address 
on two photocell pairs; check address)

1 0

Both limit switches with the same polarity

1 2

Limit switch engaged at the beginning of 
SETUP

1 5

Time-out finished

Summary of Contents for E720

Page 1: ...USB GND OPEN B CLOSE STOP FSW OP GND FSW CL 24 F C C M A I N P E N L B A T T E R Y M O T O R L A M P L O C K L O C K L O C K P R I M T R A N S F S E C T R A N S F F C A R A D I O 1 R A D I O 2 E R R O...

Page 2: ...tibility Directive Additional note This product has undergone testing in a typical standard configuration all products built by FAAC S p A Bologna 01 05 2010 The Managing Director A Marcellan 1 WARNIN...

Page 3: ...ream of the system a differential thermal breaker with adequate tripping threshold Connect the earth lead to the appropriate terminal Always separate power cables from control and safety cables push b...

Page 4: ...reverses the motion during gate closing 8 24 V Accessory power supply positive Power supply 230 V 50 Hz Power consumption from mains stand by 10 W Motor max load 6 A Accessory power supply 24 Vdc Acce...

Page 5: ...otect Safety devices during closing operate only during the automated system closing movement and are there fore suitable for protecting the closing area from the risk of impact Safety devices during...

Page 6: ...time simply by following the procedure below Install and programme the accessories with the re quired address see par 4 1 1 Cut off power to the board Connect both cables of the BUS 2EASY accessories...

Page 7: ...f a pair of closing photocells and a pair of opening photocells Connection of a pair of opening photocells Connection of a pair of closing photocells a pair of open ing photocells and a pair of openin...

Page 8: ...isplay shows again the status of the automated system 1st LEVEL PROGRAMMING Display Function Default 1 dF DEFAULT 1 Configures the parameters with DEFAULT values CU If push button F is released the va...

Page 9: ...ble from 5 with speed 5 10 with speed between 5 and 8 15 with speed 8 to 99 in 1 steps 5 10 15 minimum slowing 99 maximum slowing 20 rc SLOWING DURING CLOSING Adjusts the slowing space as a percentage...

Page 10: ...ELLS Activate the function if you want the closing photocells to lock movement and reverse it on disengagement Normally operation of the closing photocells immediately puts the gate into reverse when...

Page 11: ...ate OPENING 09 gate CLOSING 10 ACTIVE safety 11 timed output that can be activated by second radio channel see next function 12 output that can be activated by second radio channel step function 00 t1...

Page 12: ...atus display 00 CLOSED 01 OPEN 02 Stop then OPEN 03 Stop then CLOSE 04 In PAUSE 05 During opening stage 06 During closing stage 07 FAIL SAFE in progress 08 BUS 2EASY device check in progress 09 Prefla...

Page 13: ...7 8 9 a b c d e f 6 3 STORING LC RC RADIOCONTROLS ONLY FOR SOME MARKETS It is possible to store a maximum of 256 codes divided between OPEN A and OPEN B CLOSE Use the LC RC remote controls only with a...

Page 14: ...e safety inputs with a N C Normally Closed contact and the corresponding leds must therefore be ON where the automated system is in stand by they will go off when the connected device is engaged ERROR...

Page 15: ...n the rack in the direction of the motor As soon as the led for the FCA limit switch on the board goes off secure with the appropriate screws Move the gate to closing position manually leaving 40 mm f...

Page 16: ...ening stop During that stage S 1 flashes on the display The gate automatically begins to move slowly in the opposite direction and then stops when it reaches the limit switch If the limit switch reach...

Page 17: ...stores CLOSE 10 FUNCTION LOGICS The effects on the other active pulse inputs are shown in brackets LOGIC E PULSES STATUSOFAUTOMATEDSYSTEM OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL OP CLOSED opens...

Page 18: ...thegate noeffect OPEN CLOSEinhibited noeffect OPENinhibited noeffect CLOSEinhibited noeffect OPEN CLOSEinhibited LOGIC S PULSES STATUSOFAUTOMATEDSYSTEM OPENA OPENB CLOSE STOP FSWOP FSW CL FSW CL OP CL...

Page 19: ...egate closesthegate noeffect OPEN CLOSEinhibited noeffect OPENinhibited noeffect CLOSEinhibited noeffect OPEN CLOSEinhibited LOGIC B PULSES STATUSOFAUTOMATEDSYSTEM OPENA CLOSE STOP FSWOP FSW CL FSW CL...

Page 20: ...in vorliegendem Handbuch sind unverbindlich FAAC beh lt sich das Recht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der v...

Reviews: