6.2  POSITIONING OF LIMIT SWITCHES 

  To ensure correct positioning of the limit switch magnets, the control unit must be installed and correctly con-

nected with all control and safety accessories .

The operator is equipped with a magnetic limit switch sensor built directly into the electronic control board.

The gate is stopped, during opening or closure, at the moment when the polarised magnet secured to the upper part of the rack 

activates the sensor.

Assemble both magnets as shown in Fig. 19.

Prepare the operator for manual operating mode as described in chapter 8 and power the system.

  

To position the limit switch on the rack, refer to the electronic equipment instructions.

  

To avoid damage to the operator and/or interruptions in the operation of the automated system, approximately 

40 mm must be left from the mechanical limit switches.

7  TESTING THE AUTOMATED SYSTEM 

Once the operator has been installed, carry out a thorough 

operational check of all accessories and connected safety 

devices.

Press-fit the plastic covers of the operator fastening bolts, ensuring 

that the arrow is facing the gate (Fig. 20 re. 

), insert the cover 

casing (Fig. 20 re. 

) and fasten it by the two suitable side bolts 

(Fig. 20 re. 

).

Give the Customer the "User Guide" and explain the correct op-

eration and use of the gearmotor, highlighting potential high-risk 

areas of the automated system.

8  OPERATOR RELEASE/LOCK 

 During the release/lock manoeuvre, take care 

to prevent an involuntary pulse from operating 

the gate.

Proceed as follows to release the gearmotor:

1.  Turn the release clockwise as shown  in Fig. 21 re. 

. The 

release lever will move slightly away from the operator body 

(Fig. 21 re. 

)

2.  Fully lower the release lever to the mechanical stop Fig. 21 

re. 

.

3.  Carry out the opening or closing manoeuvre manually.

Summary of Contents for C720

Page 1: ...C720 C721 C720 C721...

Page 2: ...circuit break is recommended 13 Make sure that a differential switch with threshold of 0 03 A is fitted upstream of the system 14 Make sure that the earthing system is perfectly constructed and connec...

Page 3: ...AIR 10 11 ACCESSORIES 10 11 1 BATTERY KIT 10 11 2 RADIO MODULE 10 CE DECLARATION OF CONFORMITY FOR MACHINES DIRECTIVE 2006 42 EC Manufacturer FAAC S p A Address Via Calari 10 40069 Zola Predosa BOLOGN...

Page 4: ...power cut if emergency batteries are not installed or if the operator is not in service 1 Cover casing 2 Motor lock 3 Link cover 4 Motor release handle 5 Transformer 6 Foundation plate 7 Cable passag...

Page 5: ...ed plus mechanical limit switches to prevent the gate derailing The gate slide track must be linear and horizontal Manual movement of the gate must be easy throughout its travel The soil must permit s...

Page 6: ...late with GALVANISED STEEL rack NYLON rack left closure Dimensions in mm This symbol must always face to wards the gate 3 Prepare a foundation plinth as shown in Fig 7 and wall in the foundation plate...

Page 7: ...nsions in mm with rack in GALVANISED STEEL 3 Adjust the height of the gearmotor and the distance from the gate with reference to the dimensions in Fig 10 Operation required for correct fastening of th...

Page 8: ...en the rack and the gate positioning it at the top of the slot In this way the slot play will enable any adjustments to be made 3 Mark the drilling point on the gate Drill a 6 5 mm hole and apply thre...

Page 9: ...ting any work on the control board connections programming mainte nance always turn off power Observe points 10 11 12 13 14 of the GENERAL SAFETY OBLIGATIONS Follow the instructions in Fig 3 to arrang...

Page 10: ...eration of the automated system approximately 40 mm must be left from the mechanical limit switches 7 TESTING THE AUTOMATED SYSTEM Once the operator has been installed carry out a thorough operational...

Page 11: ...of the safety devices including the motor thrust force which must comply with current standards and of the release devices 10 REPAIR Contact an authorised Repair Centre for repairs 11 ACCESSORIES 11...

Page 12: ...f after the selected pause time If semi automatic operating mode has been selected a second pulse must be sent to re close the gate An opening pulse issued during the re closing stage always causes a...

Page 13: ...79 6645 faactm info faacgroup com www faac de INDIA FAAC INDIA PVT LTD Noida Delhi India tel 91 120 3934100 4199 www faacindia com IRELAND NATIONAL AUTOMATION LIMITED Boyle Co Roscommon Ireland tel 35...

Reviews: