min. 25 mm
(1) With the pre-flashing selected, movement starts after 5 seconds.
(2) If the impulse is sent during pre-flashing, the timer is reset to zero.
5.5.
FAULT CONDITIONS
The following conditions effect normal operation of the
automation:
a
microprocessor error
b
intervention of the electronic safety timer (interruption of
operation after continuous working time exceeds 255
seconds).
c
disconnection of the limit switch cable connector
•
Conditions
a
and
b
have the sole effect of causing the
automation to stop.
•
Condition
c
(indicated by the fact that both LEDs FCA
and FCC are off) prevents the card from operating:
normal operation is only resumed after the cause of the
IMPULSES
LOGICA A1
SAFETY
no effect
freezes pause until
disengagement
inverts motion
no effect
no effect
STOP
no effect
stops counting
stops
stops
no effect
GATE STATUS
CLOSED
OPEN
CLOSING
OPENING
STOPPED
OPEN
opens and recloses after
pause time (1)
recloses after 5 s (2)
inverts motion
no effect
recloses (1)
TABLE 5
LOGICA A1 (AUTOMATIC)
•
Mount the electric lock vertically on the upper guide
upright (or on the support bracket).
•
Close the gate (to about 2 cm from the mechanical travel
stop) and provisionally mount the lock plate. Fix perma-
nently only after testing the control unit, checking that the
closure limit switch works and adjusting the intensity of the
braking effect.
5.4.
DIPSWITCH SETTINGS
To program the operation of the automation, set the dipswitches
as shown in the diagram above.
Press the RESET button after all programming operations.
Operating logics
There are four operating logics available:
A1 = Automatic
S1 = Safety
S2 = Safety Plus
E = Semi-automatic
Operation of the different logics is described in tables 5-6-7-8.
Pause time
The pause time is amount of time the gate remains open
before it re-closes when an automatic control logic is selected.
Pause times include the pre-flashing time, if selected.
Operation of electric lock(s)
Allows you to choose whether the electric lock is to be activated
only before opening or also before closing. In both cases the
lock is released only when the respective limit switch is engaged
(e.g. it is released before opening only if the closure limit switch
is activated).
Pre-flashing
It is possible to select 5 seconds pre-flashing of the flashing light
before any gate movement. This serves to warn any persons in
the vicinity that the gate is about to start moving.
Install as follows:
•
Make sure that the upper guide upright is large enough to
allow the electric lock to be mounted vertically; if it is not,
install a rugged support bracket.
•
Make sure that the clearance between the lower edge of
the upper guide upright and the upper edge of the gate
is sufficient to allow the lock plate to be installed and
allows the bolt to work correctly (see fig.30).
N.B.: The values marked refer solely to the FAAC V 75 code
712654 lock and the FAAC code 720329 lock plate
Lock plate
Electric lock
Upper guide
upright(section)
Closure
Fig. 30
Pre-flashing
SW6
Yes
ON
No
OFF
1
2
3
4
5
6
Operation of electric lock(s)
SW5
Release only before opening (1 electric lock)
ON
OFF
Release before opening and release before
closing (2 electric locks required)
Logica
SW1
SW2
E1
ON
ON
A1
ON
OFF
S2
OFF
ON
S1
OFF
OFF
Pause time (sec)
Logic
A1 - S2
S1
SW3 SW4
5
15
ON
ON
10
30
OFF ON
30
60
ON OFF
120
180
OFF OFF
ON
OFF
LOGIC S1
IMPULSES
GATE STATUS
CLOSED
OPEN
CLOSING
OPENING
STOPPED
OPEN
opens and recloses after
pause time (1)
recloses immediately
(1 and 2)
inverts motion
inverts motion
recloses (1)
STOP
no effect
stops counting
stops
stops
no effect
SAFETY
no effect
recloses after 5 s
from disengagement
inverts motion
no effect
no effect
TABLE 6
LOGIC S1 (SAFETY)
LOGIC S2
IMPULSES
STOP
no effect
stops counting
stops
stops
no effect
GATE STATUS
CLOSED
OPEN
CLOSING
OPENING
STOPPED
OPEN
opens and recloses after
pause time (1)
recloses immediately
(1 and 2)
inverts motion
inverts motion
recloses (1)
SAFETY
no effect
freezes pause until
disengagement
stops and inverts motion
when disengaged (1)
no effect
no effect
TABLE 7
LOGIC S2 (SAFETY PLUS)
TABLE 8
LOGIC E1 (SEMI-AUTOMATIC)
SAFETY
no effect
no effect
inverts motion
no effect
no effect
GATE STATUS
CLOSED
OPEN
CLOSING
OPENING
STOPPED
OPEN
opens (1)
recloses (1)
inverts motion
stops
recloses (reopens when safety
devices are engaged) (1)
STOP
no effect
no effect
stops
stops
no effect
IMPULSES
LOGIC E1