= Semi-automatic
= Automatic
= Security
= “Stepped” Semi-automatic
= “Stepped” Automatic
= “Stepped”  Security
= Manned, pulsed
= Manned, constant

LEAF 1 FORCE:

 

Adjusts thrust of Motor 1.

 = minimum force

 

= maximum force (*)

press

F

The following table displays the sequence of functions 

accessible in BASIC PROGRAMMING:

BASIC PROGRAMMING

PAUSE TIME:

This has effect only when automatic logic is selected. 
Adjustable from 

 to 

 secs. in one-second 

increments.

Subsequently, display changes to minutes and tenths 
of seconds (separated by a decimal point), time 
is adjusted in 10-second increments, up to 

 

minutes max. Thus, if the unit displays 

, Pause 

Time is 2 mins. and 50 secs.

Exit from programming and return to inputs status 
monitoring.

8. Programming

To program the 455D Control Board, you have to access 

PROGRAMMING

” mode. Programming is split into two parts: 

BASIC 

and 

ADVANCED

.

LEAF 2 FORCE:

  

Adjusts thrust of Motor 2.

     = minimum force

 = maximum force (*)

LEAF 1 CLOSING DELAY:

Delays closing start of leaf 1 with respect to 
leaf 2. Adjustable from   to 

 minutes (see 

Pause Time).

TIME LEARNING (see Section 10):

Enables the selection between “simple” 
learning and “complete” (manual choice of 
deceleration and stop points) learning.

+

 

 1 s.

 

Simple Learning:

 >

 3 s.

 

Complete Learning:

OPERATING LOGICS (see tab. 3/a - h):

(*) For hydraulic operators, set force to the maximum 
level.

Basic Programming: 

To access BASIC PROGRAMMING, press  key 

F

:

•  Press and hold 

F

, the unit will display the name of the first 

function / parameter.

•  When you release the key, the unit will display the param-

eter’s current value.

•  Value can be modified with keys 

+

 and 

•  Press and hold 

F

 again, the unit will display the name of 

the next function / parameter.

•  When you reach the last function, press 

F

 to exit the pro-

gram, the display resumes monitoring input status.

•  IMPORTANT: Make sure to exit programming mode other-

wise the changes will not be saved.

Display

Function

Default

+

7. Operating Logics

This is a brief description of the main operating logics of the 

system. For a complete description please refer to Table 3

•  E (semi-automatic): This mode requires a command to 

open and a command to close. A second command 

during opening stops the gate. A second command 

during closing reopens the gate.

•  A (automatic): The gate opens on command and 

automatically closes after the pause time. A second 

command while opening is ignored; a second com-

mand during the pause phase interrupts the pause 

time; a second command during closing reopens the 

gate. A maintained open command will hold the gate 

open.

•  S (security): The security mode is like A logic except 

that a second command during opening immediately 

closes the gate. A maintained open command will not 

hold the gate open.

•  EP (semi-automatic, step by step): This mode requires 

a command to open and a command to close. A 

second command during opening or closing causes 

the gate to stop. A third command then reverses the 

previous motion of the gate.

•  B (manned, pulsed): This mode is designed for guard 

station use and requires a three button switch (pulsed) 

to open, close, and stop the gate. 

•  C (manned and constant): This mode requires con-

stant pressure switches. One to open and one to close. 

No pressure on a switch stops the gate.

Summary of Contents for 455D220A.5

Page 1: ...Board FAAC International Inc Headquarter East Coast Operations 3160 Murrell Rd Rockledge FL 32955 Tel 800 221 8278 www faacusa com FAAC International Inc West Coast Operations 357 South Acacia Avenue...

Page 2: ...be excluded Thrust Force Adjustable on 50 levels for each motor Terminal Board Inputs Open Open Free Leaf Stop Limit switch Opening Safety Devices Closing Safety Devices Power Supply Earth Terminal B...

Page 3: ...connected to this input See the next paragraph on how to connect a monitored device If this input is active when the gate is open it will prevent the leaf closing movement OP FSW Opening safety device...

Page 4: ...e connected for the system to work 1 2 5 4 3 1 2 RX CL TX CL 9 10 11 12 13 14 15 16 17 18 19 OPEN A B STP CL OP FSW 24V TX FSW 20 21 W L LOCK 1 2 5 4 3 1 2 RX OP TX OP 1 2 5 4 3 1 2 RX CL TX CL 9 10 1...

Page 5: ...ct Typically these photocells work in combination with other monitored photocell pro tecting closing or opening entrapment zones In that case they can t be monitored so they can only protect against p...

Page 6: ...ill display the param eter s current value Value can be modified with keys and Press and hold F again the unit will display the name of the next function parameter When you reach the last function pre...

Page 7: ...d OFF when gate is closed the output is ON when the gate is open or in pause OFF in all other conditions the output is ON when the gate is closed OFF in all other conditions All other values correspon...

Page 8: ...nd black wires on the 455 D control board 7 Check force setting of the motors modify if necessary Note For hydraulic operators like the 400 force should be programmed to maximum level 50 8 Stop leaf m...

Page 9: ...2 stops at opening and immediately begins its closing movement 5 Slow down at closing of leaf 2 6 Leaf 2 stops at closing and leaf 1 begins its closing movement 7 Slow down at closing of leaf 1 8 Leaf...

Page 10: ...i t n o c e s a e l e r n o d n a s k c o L g n i n e p o D E K C O L 3 f a e l e h t s e s o l C t c e f f e o N d e l b a s i d N E P O t c e f f e o N t c e f f e o N d e l b a s i d N E P O E c i...

Page 11: ...diately stops operation NB Effects on other active pulse inputs in brackets P A c i g o L S E S L U P S U T A T S E T A G A N E P O B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V...

Page 12: ...OR 1 MOTOR 2 CL COM OP 1 2 3 4 5 6 7 8 20 21 FCA1 FCA2 FCC2 FCC1 F J2 J6 J4 J5 J3 N L MAIN OP CL 24 V FSW B STOP A TX FSW 9 10 11 12 13 14 15 16 17 18 19 J1 PHOTO OP OPEN DEVICES PHOTO CL 24VDC RX PHO...

Page 13: ...prewired enclosure comes with dedicated terminal blocks for the connection of safety photocells that can be monitored by the control board for presence and correct operation One closing and one openi...

Page 14: ...ections If using non FAAC relay make sure the minimum switch volt age is less than 12Vac SHADOW INPUT Line Voltage MOTOR ON 24 VDC SHADOW LOOP 120V or 230 AC SHADOW KIT OPTION 8 7 10 1 2 5 Shadow Loop...

Page 15: ...sume for them any other liability in connection with the sale or use of the products of beyond that extended herein The warranty hereinabove set forth shall not be deemed to cover maintenance parts in...

Page 16: ...2021 FAAC International Inc All Rights Reserved Published in Jan 2021 455D 532218 Rev B US...

Reviews: