4

Entrapment protection

To comply with the UL325 standard for gate operators every 

entrapment zone, as defined in ASTMF2200, must be pro-

tected by two independent entrapment protection devices. 

One of the devices is inherent in the FAAC operators or the 

control board design, the other can be external, like a pho-
tocell or an edge sensor.

See the following picture for the photocells positioning:

Closing Safety Devices

Opening Safety 

Devices

Opening Safety Devices:

 

Are active only during the gate opening movement, and 

are suitable for protecting the area between the opening 

leaves and fixed obstacles (walls, etc) agains the risk of 
entrapment

Closing Safety Devices: 

Are active only during the gate closing movement, and are 

suitable for protecting the closing area against the risk of 
entrapment.

Monitored Devices: 

Additionaly the UL325 standard requires that every external 

entrapment protection device must be monitored for 

presence and correct operation. The closing safety devices 

are always monitored, see the following picture for the wiring 

of a pair of photocells as closing safety devices. 

NOTE: one closing safety device must always be connected 
for the system to work.

1

2

5

4

3

1

2

RX CL

TX CL

9 10 11 12 13 14 15 16 17 18 19

OPEN

A

B STP CL OP

FSW

- - -

+24V

+

+ -TX

FSW

20 21

W.L.

LOCK

-

+

-

+

1

2

5

4

3

1

2

RX OP

TX OP

-

+

-

+

-

+

-

+

+

+

1

2

5

4

3

1
2

RX CL

TX CL

9 10 11 12 13 14 15 16 17 18 19

OPEN

A

B STP CL OP

FSW

- - -

+24V

+

+ -TX

FSW

20 21

W.L.

LOCK

-

+

-

+

-

+

+

Connection of One Pair of Monitored Closing 

Photocells and One Pair of Monitored Opening 

Photocells

Connection of One Pair of Monitored Closing Photocells

F

+

+

ADVANCED PROGRAMMING

OPENING FAIL SAFE:

If this function is activated, it enables the 
monitoring of the opening safety photocell 

before he opening movement. If the test fails 
the gate does not open.

 

= Active 

 = Disabled

Display

Function

Default

Monitoring of the opening safety devices must be enabled 

in the board configuration. To enable it enter in advanced 

programming by pressing and holding “F” and then press 

“+”, scroll to the “FS” parameter and select “Active”.

6. Connection of Safety devices

16” or less

If an additional monitored opening safety device is 

needed it can be connected to the STP input. The “OP” 

parameter in the board configuration must be set to active 

1

2

TX OP 2

9 1

0

1

1

2 13 14 15 16 17 18 19

OPEN

A

B

STP

CL

OP

FSW

-

-

-

+24V

+

+ -TX

FSW

20 21

W.L.

LOCK

-

+

5

4

3

1
2

RX OP 2

-

+

-

+

+

1

OPENING No. 2 FAIL SAFE:

When enabled the STOP input can be used for 

the connection of a second monitored opening 
safety device. 

 = Active 

 = Disabled

Summary of Contents for 455D220A.5

Page 1: ...Board FAAC International Inc Headquarter East Coast Operations 3160 Murrell Rd Rockledge FL 32955 Tel 800 221 8278 www faacusa com FAAC International Inc West Coast Operations 357 South Acacia Avenue...

Page 2: ...be excluded Thrust Force Adjustable on 50 levels for each motor Terminal Board Inputs Open Open Free Leaf Stop Limit switch Opening Safety Devices Closing Safety Devices Power Supply Earth Terminal B...

Page 3: ...connected to this input See the next paragraph on how to connect a monitored device If this input is active when the gate is open it will prevent the leaf closing movement OP FSW Opening safety device...

Page 4: ...e connected for the system to work 1 2 5 4 3 1 2 RX CL TX CL 9 10 11 12 13 14 15 16 17 18 19 OPEN A B STP CL OP FSW 24V TX FSW 20 21 W L LOCK 1 2 5 4 3 1 2 RX OP TX OP 1 2 5 4 3 1 2 RX CL TX CL 9 10 1...

Page 5: ...ct Typically these photocells work in combination with other monitored photocell pro tecting closing or opening entrapment zones In that case they can t be monitored so they can only protect against p...

Page 6: ...ill display the param eter s current value Value can be modified with keys and Press and hold F again the unit will display the name of the next function parameter When you reach the last function pre...

Page 7: ...d OFF when gate is closed the output is ON when the gate is open or in pause OFF in all other conditions the output is ON when the gate is closed OFF in all other conditions All other values correspon...

Page 8: ...nd black wires on the 455 D control board 7 Check force setting of the motors modify if necessary Note For hydraulic operators like the 400 force should be programmed to maximum level 50 8 Stop leaf m...

Page 9: ...2 stops at opening and immediately begins its closing movement 5 Slow down at closing of leaf 2 6 Leaf 2 stops at closing and leaf 1 begins its closing movement 7 Slow down at closing of leaf 1 8 Leaf...

Page 10: ...i t n o c e s a e l e r n o d n a s k c o L g n i n e p o D E K C O L 3 f a e l e h t s e s o l C t c e f f e o N d e l b a s i d N E P O t c e f f e o N t c e f f e o N d e l b a s i d N E P O E c i...

Page 11: ...diately stops operation NB Effects on other active pulse inputs in brackets P A c i g o L S E S L U P S U T A T S E T A G A N E P O B N E P O P O T S S E C I V E D Y T E F A S G N I N E P O S E C I V...

Page 12: ...OR 1 MOTOR 2 CL COM OP 1 2 3 4 5 6 7 8 20 21 FCA1 FCA2 FCC2 FCC1 F J2 J6 J4 J5 J3 N L MAIN OP CL 24 V FSW B STOP A TX FSW 9 10 11 12 13 14 15 16 17 18 19 J1 PHOTO OP OPEN DEVICES PHOTO CL 24VDC RX PHO...

Page 13: ...prewired enclosure comes with dedicated terminal blocks for the connection of safety photocells that can be monitored by the control board for presence and correct operation One closing and one openi...

Page 14: ...ections If using non FAAC relay make sure the minimum switch volt age is less than 12Vac SHADOW INPUT Line Voltage MOTOR ON 24 VDC SHADOW LOOP 120V or 230 AC SHADOW KIT OPTION 8 7 10 1 2 5 Shadow Loop...

Page 15: ...sume for them any other liability in connection with the sale or use of the products of beyond that extended herein The warranty hereinabove set forth shall not be deemed to cover maintenance parts in...

Page 16: ...2021 FAAC International Inc All Rights Reserved Published in Jan 2021 455D 532218 Rev B US...

Reviews: