Page 9 

November, 2003 
455 D Control Panel Installation Instructions 

ADVANCED PROGRAMMING 

 

Display Function 

Default 

 

M

AXIMUM

  T

ORQUE

 

AT

  I

NITIAL

  T

HRUST

:  

The motors operate at maximum 

torque (ignoring the torque setting) 

at  start  of  movement.    Useful  for 

heavy leaves. 

4 = Enable 

No = Disabled 

 

 

L

AST

 S

TROKE

 

AT

 C

LOSING

The motors are activated at full 

speed for 1s to facilitate locking of 

the electric lock. 

4 = Enable 

No = Disabled 

 

 

R

EVERSING

 S

TROKE

Before opening, while the gate is 

closed, the motors thrust to close 

for 2 s thus facilitating release of the 

electric lock. 

4 = Enable 

No = Disabled

 

 

 

L

EAF

 2 O

PENING

 D

ELAY

 (2

S

): 

Enables delayed start (at opening) of 

leaf 2, avoiding interference between 

leaves. 

4 = Enable 

No = Disabled

 

 

 

F

AIL

 S

AFE

If  this  function  is  activated,  it 

enables a function test of the 

phot ocells befor e an y gat e 

movement.  If the test fails 

(photocells not serviceable), the gate 

does not start the movement. 

 

4 = Enable 

No = Disabled

 

 

 

P

RE

 F

LASHING

 (5

S

): 

Activates the flashing lamp for 5s 

before start of movement. 

 

4 = Enable 

No = Disabled

 

 

 

E

LECTRIC

 L

OCK

 

ON

 L

EAF

 2:   

For using the electric lock on leaf 2 

instead of on leaf 1.  

 

4 = Enable 

No = Disabled

 

 

F

+

Display 

Function Default 

 

I

NDICATOR

-L

ICHT

If 0 is selected, the output functions 

as a standard indicator-light (lighted 

at opening and pause, flashing at 

closing, and off when gate closed).  

Different figures correspond to timed 

activation of the output, which can be 

used (via a relay) to power a courtesy 

lamp.    Time  can  be  adjusted  from  0 

to 59s in 1s increments, and from 1.0 

to 4.1 min. in 10s steps. 

 

0 = Standard Indicator-Light 

From 1 to 4.1 = Timed Output 

 

 

 

C

LOSING

  P

HOTOCELLS

 

REVERSE

 

AT

 

RELEASE

Enable this function if you want the 

closing photocells to stop the gate 

movement and reverse it after the 

beam is cleared. Default setting is 

immediate reverse. 

 

4 = Enable 

No = Disabled

 

 

 

A.D.M.A.P. F

UNCTION

If this function is enabled, the safety 

devices operate in compliance with 

French standard NFP 25/362. 

 

4 = Enable 

No = Disabled

 

 

 

A

SSISTANCE

  R

EQUEST

  (

COMBINED

 

WITH

 

NEXT

 

FUNCTION

): 

If activated, at the end of countdown 

(settable with the next function, i.e. 

“Cycle programming”) it effects 8s of 

pre-flashing at every Open pulse (job 

request).  Can be useful for setting 

scheduled maintenance jobs. 

 

4 = Enable 

No = Disabled

 

 

 

C

YCLE

 P

ROGRAMMING

For setting count down of system 

operation cycles.  Settable (in 

thousands) from 0 to 99 thousand 

cycles.  The displayed value is 

updated as cycles proceed.  This 

function can be used to check use of 

the board or to exploit the 

“Assistance Request” function.

 

 

 

E

XIT

 P

ROGRAMMING

Exit from programming and return to 

display of inputs status. 

 

Summary of Contents for 455 D

Page 1: ...es 10 Learning of Normal Times 10 Learning Times with Gatecoder 10 Automated System Test 11 Logic Tables of 455 D Control Panel 12 Safety in Gate Design 14 Maintenance 14 Limited Warranty 16 T H E 4 5...

Page 2: ...reaker switch and for making sure that the entire gate system meets all applicable electrical codes The installer should refer to the installation manual for a given operator for more information NOTE...

Page 3: ...e each leg of the capacitor supplied to terminals 2 3 Note If you want to delay the closing of one gate leaf in a two leaf gate design be sure to connect its operator to Motor 1 In order to wire motor...

Page 4: ...pplying power to accessories through terminals 17 or 18 and 14 or 15 or 16 on terminal block J1 In most cases this source can be used to power 24 VDC accessories NOTE The 455 D control panel allows a...

Page 5: ...OP_B Partial Opening should illuminate only when an activating signal is sent for 2 and 1 gate leaves respectively STOP should be illuminated except when the stop button is pressed FSWOP and FSWCL sh...

Page 6: ...is set at less than the leaf delay time the delayed leaf closes at the end of the closing time Page 6 November 2003 455 D Control Panel Installation Instructions opening and closing respectively are...

Page 7: ...ls f or opening 1 2 1 2 3 4 5 17 13 19 14 17 Additional Reversing Devices TX RX 1 2 1 2 3 4 5 19 17 12 19 17 Additional Reversing Devices TX RX 1 2 19 12 17 15 Additional Reversing Devices 8 7 Safety...

Page 8: ...and if you release it the value that can be modified with keys and When you reach the last function press the F key to exit the program and the display resumes showing the status of the inputs The tab...

Page 9: ...ed the output functions as a standard indicator light lighted at opening and pause flashing at closing and off when gate closed Different figures correspond to timed activation of the output which can...

Page 10: ...automatically when the opening positive stop is reached and the display stops flashing The procedure has ended and the gate is ready to operate using default slow down automatically set by the control...

Page 11: ...top the operator will automatically shut off An open command must be given to start closing gate operator 2 When gate operator 2 reaches the position that you want it to slow down an open command must...

Page 12: ...t Closed Opens both leaves and closes them after pause time Opens single leaf connected to Motor 1 and closes it after pause time No effect No effect No effect Off Opening Closes both leaves Closes le...

Page 13: ...or 1 No effect opening is inhibited No effect opening is inhibited No effect opening is inhibited Off Opening Stops Stops Stops Stops gate closes when reversing device no longer trig gered No effect O...

Page 14: ...rians should not use a vehicular gate system Prevent such inappropriate use by installing separate gates for pedestrians The operating controls for an automatic gate must be secured to prevent the una...

Page 15: ...Page 15 November 2003 455 D Control Panel Installation Instructions This page is left blank intentionally...

Page 16: ...subject to misuse negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or oth...

Reviews: