E (semi-automatic):

 

This mode requires a 

command to open and a command to close.  

A second command during opening stops the 
gate.  A second command during closing 
reopens the gate. 

 

• 

EP (semi-automatic, step by step):

 

This 

mode requires a command to open and a 
command to close. A second command 
during opening or closing causes the gate to 

stop. A third command then reverses the 
previous motion of the gate. 

 

• 

B (manned, pulsed):

 

This mode is designed 

for guard station use and requires a three-

button switch (pulsed) to open, close, and 
stop the gate. 

 

• 

C (manned and constant):

 

This mode 

requires constant pressure switches. One to 

open and one to close. No pressure on a 
switch stops the gate. 

 

The three programming push buttons allow the 
programming of the torque (or pressure), the pause 
time between opening and closing, and the leaf delay 

on closing. 
 

WARNING

Turn the main power off before you 

make any electrical connections. 

 
For all FAAC hydraulic operators using the 455 D 
control panel, the force 

must

 be set at its maximum 

setting of 50 in order to supply the correct voltage to 
the operator.   
 

P

AUSE

  T

IME

:  

The pause time between opening and 

closing can be adjusted from 0 seconds to 4 minutes.  

Time is adjusted in one-second increments from 0—
59 seconds.  When 60 seconds is reached, time is 
adjusted in 10 second increments up to 4 minutes.  

i.e. if display shows 2.5, it means 2 minutes and 50 
seconds. 
 

L

EAF

  D

ELAY

You may choose to delay one leaf on 

closing for overlapping gate leaves. Be sure the 
operator on the leaf for delayed closing is connected 
to Motor 1. On opening, the leaf connected to Motor 2 

is delayed 2.5 sec.  
 

N

OTE

: If an opening leaf delay is desired, it must 

be enabled in the Advance Programming. 

 

However, if enabled, you cannot 

adjust

 this 

opening delay of the operator connected to 

Motor 2.  
 

The closing leaf-delay time is adjustable from 0 to 4 

minutes.  

 

N

OTE

If the opening/closing time is set at less 

than the leaf delay time, the delayed leaf closes 
at the end of the closing time. 

opening and closing, respectively, are triggered. Use 

the LEDs and the next table to determine if the 
accessory devices you have installed are operating 

properly. 

 

Electric Locks: 

An electric lock can be wired to 

the 455 D in 

terminals 18 and 21 (12Vac pulsed 

provided). If a reversing stroke is needed to allow the 
electric lock to release, this must be done in advanced 
programming. 

 
See page 19 for the connections for a magnetic locking 
device. 

 

W

ARNING

  L

IGHT

Connect a warning light to 

terminals 18 and 20 in the group labeled 

W.LIGHT

 

in terminal block J1 and J5. The terminals provide 
an output voltage of 24 VDC, maximum power 3 

Watts. This output voltage will power most 24 VDC 
warning lights. 
 

N

OTE

: The behavior of the warning light varies 

according to the logic you have set. 

 

L

OGICS

 A, S, E, EP, 

AND

  B

The warning light is on 

steadily during opening and the pause phase. During 
closing, the light flashes. 
 

L

OGIC

  C

The warning light is on steadily during 

opening and flashes during closing. 

S

ET

 O

THER

 O

PERATING

 C

ONTROLS

 

 
WARNING

! Turn the main power off before you 

make any electrical connections. 

 

You need to program the control panel for your gate's 
operation. The 455 D Control Panel has on board 

programming that controls a wide range of functions. 
 

O

PERATING

 L

OGICS

 

 

N

OTE

: The 455 D Control Panel provides inputs 

for opening reversing devices and closing 

reversing devices. FAAC strongly recommends 
the use of reversing devices, such as photocells 
or other non-contact sensors. 

 

• 

A (automatic):

 

The gate opens on command 

and automatically closes after a pause phase. A 
second command while opening is ignored; a 
second command during the pause phase 

interrupts the pause time; a second command 
during closing reopens the gate.  A maintained 
open command  will hold the gate open. 

 

• 

S (security):

 

The security mode is like A logic 

except that a second command during opening 
immediately closes the gate.  A maintained 
open command will not hold the gate open. 

Page 18 

January,  200 4 

412 O pe rator And  

455 D  Control Panel I nst allatio n M anual   

T

HE

 455 D C

ONTROL

 P

ANEL

 I

NSTALLATION

 I

NSTRUCTIONS

 

Summary of Contents for 412 Compact

Page 1: ...l the Operator 7 Install the 455 D Control Panel 10 Exploded View 412 12 412 Parts List 13 The 455 D Control Panel General Description 14 Installing the 455 D Control Panel 14 Connect the Main Power S...

Page 2: ...affected by the size of the gate how often it is used and how fast the gate operates 2 The operator you choose to install on your gate must be designed for the type and size of your gate and for the...

Page 3: ...power before making any attempt to repair it 4 Do not attempt to impede the movement of the gate You may injure yourself as a result 5 This equipment may reach high temperatures during operation ther...

Page 4: ...aximum leaf swing deg 110 Thrust and traction3 ft lb Nm 0 294 0 400 0 235 0 320 Stroke in cm 11 3 8 29 Rod speed 4 in sec cm sec 3 4 1 9 5 8 1 6 Thermal cut out deg F deg C 284 140 Operator dimensions...

Page 5: ...s marked DX Be sure to install each on the proper gate leaf see Figure 2 2 Protective covers for the worm screw housing of the operator 1 Package of mounting hardware 2 Rear mounting brackets 2 Rear m...

Page 6: ...anism that precisely controls the force transmitted to the gate leaf through the 412 Operator The Manual Release mechanism is a key operated device that disengages or engages the worm screw drive of t...

Page 7: ...e where the operators are mounted The operator attached to the hinge on the left of the gate must be an SX model If the hinge is on the right side the DX model must be installed Installing the operato...

Page 8: ...front mounting bracket with the short pin and one snap ring on the bottom and one snap ring on the top see Figure 9 11 13 16 in 30 cm 4 in 10 cm 5 29 32 in 15 cm Figure 6 The required dimensions of th...

Page 9: ...Gate post or column Steel elbow A B C D F Centerline of gate leaf E Mounting Dimensions 90 deg Swing 110 deg Swing A 5 3 4 in 14 5 cm 4 7 8 in 12 5 cm B 5 3 4 in 14 5 cm 4 7 8 in 12 5 cm WARNING A an...

Page 10: ...OPERATOR COVER Once the operator is attached to the gate leaf you next prepare the cover for installation Caution If you did not correctly establish the orientation of the gate leaf and properly inst...

Page 11: ...d 455 D Control Panel Installation Manual 1 Operator Wire Gauges for Given Voltage 2 Control Panel 220 VAC 115 VAC 3 Photocell A 2 18 AWG A 2 18 AWG 4 Switch B 4 14 AWG B 4 14 AWG 5 Junction box see t...

Page 12: ...Page 12 January 2004 412 Operator And 455 D Control Panel Installation Manual The 412 Compact Operator...

Page 13: ...p Protective Cover SX 1 8 727147 End Cap Protective Cover DX 1 9 N A Nickel Plated Self Tapping Screw 3 5 x 9 5 mm 3 10 2705 Capacitor For 115 v 25 f 1 10 2707 Capacitor For 220 v 8 f 1 11 727216 Prot...

Page 14: ...that the entire gate system meets all applicable electrical codes The installer should refer to the installation manual for a given operator for more information NOTE An installation is U L compliant...

Page 15: ...e to 2 and the red wire to 3 Wire each leg of the capacitor supplied to terminals 2 3 Note If you want to delay the closing of one gate leaf in a two leaf gate design be sure to connect its operator t...

Page 16: ...in power and send an activating signal to the operator The gate leaf or leaves should open If a gate leaf closes then you need to turn off the main power and reverse the connection of the red and blac...

Page 17: ...e motors without a closed circuit between 11 14 The LED Indicators The nine light emitting diodes LEDs on the control panel can be used to check for the proper function of the devices attached to the...

Page 18: ...he delayed leaf closes at the end of the closing time opening and closing respectively are triggered Use the LEDs and the next table to determine if the accessory devices you have installed are operat...

Page 19: ...ev ices 14 9 C NO Rev ersing Photocells f or opening 1 2 1 2 3 4 5 17 13 19 14 17 Additional Reversing Devices TX RX 1 2 1 2 3 4 5 19 17 12 19 17 Additional Reversing Devices TX RX 1 2 19 12 17 15 Add...

Page 20: ...he value that can be modified with keys and When you reach the last function press the F key to exit the program and the display resumes showing the status of the inputs The table on page 21 shows the...

Page 21: ...ou sands from 0 to 99 thousand cy cles The displayed value is up dated as cycles proceed This func tion can be used to check use of the board or to exploit the Assistance Request function EXTRA WORK T...

Page 22: ...ay stops flashing LEARNING OF OPERATING TIMES WARNING During the learning procedure the safety devices are disabled Therefore any and all traffic must be avoided in the path of the gate leaf s NOTE Pr...

Page 23: ...and must be given to start the slow down phase When the gate operator reaches its positive stop the operator will automatically shut off An open command must be given to start closing gate operator 2...

Page 24: ...g Reversing Device s Warning Light Closed Opens both leaves and closes them after pause time Opens single leaf connected to Motor 1 and closes it after pause time No effect No effect No effect Off Ope...

Page 25: ...s in hibited No effect opening is inhibited No effect opening is inhibited Off Opening Stops Stops Stops Stops gate closes when reversing device no longer trig gered No effect On Opened Closes both le...

Page 26: ...directions before the automatic operator is installed An automatic operator should be installed on the inside of the property fence line Do not install the operator on the public side of the property...

Page 27: ...OPENS BUT DOES NOT CLOSE SOLUTION Make sure you have selected the desired operating mode Verify that the reversing devices are working properly FSWOP and FSWCL should be illuminated except when a rev...

Page 28: ...rdance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceeding those set forth in the specifications for such product s...

Reviews: