4. PROGRAMMING

  

OPERATING LOGIC

   DS 1:  SW 1 - SW 2 -  SW 3  

 

LOGIC

SW 

1

SW 

2

SW 

3

PAUSE 

TIME

DESCRIPTION

E  (default)

Semiautomatic

OFF OFF OFF

NO

One command opens, the next one closes. A command du-

ring opening stops the gate

A     

Automatic

ON

ON

ON

0 - 4

min

One command opens, waits for the pause time an then closes 

automatically

S    

Security

OFF OFF ON

0-4

 min

One command opens, waits for the pause time and then clo-

ses automatically. If the closing safety is activated or another 

command is given during the pause time it closes   

EP   

 Semiautomatic 

step by step 

OFF ON OFF

NO

One command opens, the next one closes. During the move-

ment a command stops the gate

AP  

 Automatic 

step by step

OFF ON

ON

0-4 

min

One command opens, waits for the pause time and then clo-

ses automatically.  A command during the pause time holds 

the gate open

SP 

Security 

step by step

ON OFF OFF

0-4 

min

One command opens, waits for the pause time and then 

closes automatically. If the closing safety is activated during 

pause time the gate closes in 5 s.  A command during pause 

time holds open the gate

Manned Pulsed 

ON OFF ON

NO

An open A command opens the gate, an open B command 

closes the gate

Manned Constant

ON

ON OFF

NO

Holding open A active opens the gate, holding Open B active 

closes the gate 

       For more details on the operating logics please refer to Chapter 12 - Function Logics

4.1  DIP SWITCH DS1 SETTINGS FOR OPERATING LOGIC

A7

E024U CONTROL BOARD

(800) 878-7829

www.FastGateOpeners.com

Summary of Contents for 202025

Page 1: ...E024 U Control Board UL325 UL991 800 878 7829 www FastGateOpeners com ...

Page 2: ...amming With trimmers dipswitches and pushbutton RADIO Connector for the radio receiver BATTERY Connector for the backup battery J24 Jumper to disable battery charging With the jumper present the battery is charged POWER SUPPLY DC Power supply input TR1 to TR6 Programming Trimmers 24 LED DC power indicator SW1 SETUP Pushbutton for automatic setup DS1 DS2 Programming dipswitches LED ERROR Troublesho...

Page 3: ...8 24 24 Vdc positive 9 OUT Programmable output See DS1 SW 11 12 10 FCA 1 Open limit switch Motor 1 11 GND 24 Vdc negative 12 FCC 1 Close limit switch Motor 1 13 FCA 2 Open limit switch Motor 2 14 GND 24 Vdc negative 15 FCC2 Close limit switch Motor 2 LAMP LAMP Audio alarm output DS1 SW11 OFF Output for flashing light 24Vdc 15W max DS1 SW11 ON LOCK LOCK Output for electrical lock max 5A pulse DS2 S...

Page 4: ...ments The E024U board allows the connection of several safety devices for example photocells With photocells you can activate the FAILSAFE function which before each movement of the ope rator tests each fotocells In case the test fails the movement is inhibited To activate this function set to ON the dip switch N 11 and 12 of DS1 and connect the negative of the transmitter to the OUT pin No 9 Fig ...

Page 5: ... the transmitters to OUT pin 9 and set dip switch 11 and 12 to ON on DS1 When using the FAIL SAFE mode also the safety inputs not used FSW CL FSW OP must be connected to OUT pin No 9 To use the FAIL SAFE mode connect the negative power supply of the transmitters to OUT pin 9 and set dip switch 11 and 12 to ON on DS1 RX Photocell Receiver TX Ptotocell Transmitter CL Closing OP Opening RX Photocell ...

Page 6: ...air of opening photocells Other optional safety devices to connect in series Fig A10 Fig A11 Fig A12 To use the FAIL SAFE mode connect the ne gative power supply of the transmitters to OUT pin 9 and set dip switch 11 and 12 to ON on DS1 When using the FAIL SAFE mode also the safety inputs not used FSW CL FSW OP must be connected to OUT pin No 9 RX Photocell Receiver TX Ptotocell Transmitter CL Clo...

Page 7: ...and stops the gate AP Automatic step by step OFF ON ON 0 4 min One command opens waits for the pause time and then clo ses automatically A command during the pause time holds the gate open SP Security step by step ON OFF OFF 0 4 min One command opens waits for the pause time and then closes automatically If the closing safety is activated during pause time the gate closes in 5 s A command during p...

Page 8: ...ting position If in the successive movement an obstacle is detected again the board will be put in alarm mode and won t take any more commands until the STOP input is activated Alarm Reset or power is cycled TR 5 PAUSE TIME ADJUSTMENT 0 4 min Turn clockwise to increase the pause time TR6 CLOSING DELAY OF LEAF 1 OVER LEAF 2 ADJUSTMENT 0 15 sec Turn clockwise to increase the delay TR1 FORCE ADJUSTME...

Page 9: ...F the gate movement will be reversed as soon as the safety is active with SW8 ON the gate will stop when the safety is active and it will reverse only when the safety is deactivated again immediate reverse default OFF reverse when cleared ON PREFLASHING SW 9 This function activates the flashing lamp for 5s before the movement of the gate inactive default OFF active for 5 sec ON EXTRA SENSITIVITY T...

Page 10: ...F ON 415 390 770 ON OFF OFF DS 2 LOCK OUTPUT MODE OUTPUT MODE SW 4 Active only for 3 sec after an open impulse from gate closed OFF Active always except 3 sec before an opening ON SETTING DL1 DL2 DL3 DL4 DL5 J24 IMPORTANT BUS DEVICE 4 4 DIP SWITCH DS2 SETTINGS FOR OPERATOR TYPE AND LOCK MODE 5 LED DIAGNOSTICS A10 E024U CONTROL BOARD 800 878 7829 www FastGateOpeners com ...

Page 11: ...USB key inserted and software Update in progress DON T Remove the USB key 7 RESERVED 8 LED DL 14 OPEN A INPUT N O OPEN A active OPEN A not active LED DL 15 OPEN B INPUT N O OPEN B active OPEN B not active LED DL 16 STOP INPUT N C STOP non active STOP active or wiring error LED DL 17 FSW CL INPUT N C Closing safety devices clear Closing safety devices triggered or wiring error LED DL 18 FSW OP INPU...

Page 12: ... the encoder 6 FAIL SAFE FAILED Verify the photocells wiring and alignement 7 BOARD THERMAL PROTECTION ACTIVE Turn off the board and wait until the components cool down 8 MAX RUN TIME REACHED WITHOUT FINDING THE POSITIVE STOP 10 min Verify that the operator manual release is not engaged Verify that the board recognizes the mechanical stop in case redo the setup procedure The diagnostic LED shows o...

Page 13: ... is already stored in memory Leaf 1 starts to slow down and stops when it reaches the mechanical stop or FCC1 12 The manual time learning procedure is complete 15 15 32 6 7 32 17 15 32 The E024U board is supplied on a panel that fits in a 16x14 enclosure On the back panel are installed the control board the power supply and additional accessories Power Supply AC connection Power outlet and switch ...

Page 14: ...the fac tory consult with FAAC Tecnical Support for 230V wiring options 230V 115V The E024U board allows the connection of a 24V backup bat tery to provide power to operate the gate during blackouts For more details about how the boards handles the loss of main power and how to configure its behaviour please see par 4 3 and DS1 switch 7 To connect the battery use the provided cable and plug it on ...

Page 15: ...OSE OPEN IN PAUSE reloads pause time 1 reloads pause time of released leaf recloses leaves immediately stops operation no effect recharges pause time CLOSE disa bled recharges pause time CLOSE disa bled CLOSING reopens leaves immediately reopens leaves immediately no effect stops operation no effect reverses at opening stops and opens at release saves CLOSE BLOCKED closes leaves closes leaves clos...

Page 16: ...ect recharges pause time CLOSE disa bled recharges pause time CLOSE disa bled CLOSING reopens leaves immediately reopens leaves immediately no effect stops operation no effect reverses at opening see DS1 SW8 stops and opens at release OPEN stops saves CLOSE BLOCKED closes leaves closes leaves closes leaves no effect OPEN CLOSE disabled no effect OPEN disa bled no effect CLOSE disa bled no effect O...

Page 17: ...he leaves no effect no effect stops operation no effect reverses at opening stops and opens at release saves OPEN CLOSE BLOCKED opens the leaves closes leaves closes leaves no effect OPEN CLOSE disabled no effect OPEN disabled no effect CLOSE disa bled no effect OPEN CLO SE disabled LOGIC SP PULSES SYSTEM STATUS OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL OP CLOSED opens and clo ses after pause ...

Page 18: ...ubject to misuse negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceeding those set forth in the specifications for such product s Neither FAAC S p A nor FAAC International Inc shall be liable for any loss or damage whatsoever resulting directly or indirectl...

Reviews: