9
1.9 Configuration Tables
Baud Rate Setting (CC)
Code
03
04
05
06
07
08
09
0A
Baud rate
1200
2400
4800
9600
19200
38400
57600
115200
Analog Input Type Setting (TT)
Code
Range
Format
+F.S.
Zero
-F.S.
00
-15~+15mV
Engineer unit
+15.000
+00.000
-15.000
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
01
-50~+50mV
Engineer unit
+50.000
+00.000
-50.000
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
02
-100~+100mV
Engineer unit
+100.00
+000.00
-100.00
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
03
-500~+500mV
Engineer unit
+500.00
+000.00
-500.00
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
04
-1~+1V
Engineer unit
+1.0000
+0.0000
-1.0000
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
05
-2.5~+2.5V
Engineer unit
+2.5000
+0.0000
-2.5000
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
06
-20~+20mA
Engineer unit
+20.000
+00.000
-20.000
% of F.S.R.
+100.00
+000.00
-100.00
2’s complement
7FFF
0000
8000
Data Format Setting (FF)
7
6
5
4
3
2
1
0
FS
CS
reserved
DF
Key
Description
DF
Data format
00: Engineering unit
01: % of FSR (full scale range)
10: 2’s complement hexadecimal
CS
Checksum setting
0: Disabled
1: Enabled
FS
Filter setting
0: 60Hz rejection
1: 50Hz rejection
Note
: The reserved bits should be zero.