background image

3.7 Wall mounting of chimney fan

 

y

When mounting the chimney fan on a wall, the installation instructions for 

installation on a steel chimney should be followed. Use of the adapter SCA can 

make the installation easier, but is not a requirement.

 

y

To ease installation, detach the fan base by removing the bolts holding the hinges 

together. Center the fan base over the outlet and bolt the base onto the wall with 

the hinges pointing upwards.

 

y

After mounting the base securely, attach the fan motor housing by reassembling 

the fan hinges. Seal with silicone all around the fiber mat to prevent rain from 

entering the flue.

 

3.8 Installation of Proven Draft Switch (PDS)

 

y

A safety system must be interlocked with the appliance(s). The safety system could 

utilize a Proven Draft Switch, a thermal switch or a flow switch. The device must be 

interlocked with the heating appliance so it shuts down in case of insufficient draft, 

fan failure or power failure. Please refer to the PDS Installation Manual if this control 

is used. 

 

y

For more information on alternative safety systems, please contact 

exodraft a/s

.

 

y

The figure shows the location of the probe for the PDS. Location is important to 

make sure there is enough pressure or draft available for the switch to work.

NOTE

A safety device that prevents the heating appliance operation, in case of a power failure or 

inadequate draft situation, must be installed.

Bolt

Bolt

9

3000270  RS gas and oil 20210818 - international

Summary of Contents for RS 009

Page 1: ...ation Chapters 1 2 Mechanical installation Chapter 3 Electrical installation Chapter 4 Start up and configuration Chapter 5 Maintenance and troubleshooting Chapter 6 READ AND SAVE THESE INSTRUCTIONS R...

Page 2: ...g place 5 This unit must be grounded How to use this manual This installation manual does not contain any system design documentation System design documentation is available from exodraft Accessories...

Page 3: ...ney fan must be interlocked with the connected appliance s to insure proper combustions and to avoid flue gas spillage 1 2 Shipping The packing list attached to one of the packages clearly lists all i...

Page 4: ...4 422 478 C in 10 8 13 5 15 5 17 4 mm 275 344 395 441 D in 3 0 3 3 3 9 3 9 mm 75 85 100 100 E in 9 4 11 6 13 5 15 4 mm 238 294 342 391 Temperature Rating Interm 575 F 300 C Cont 482 F 250 C Capacity 1...

Page 5: ...st be provided for combustion otherwise improper operation and inadequate venting of deadly flue gases may result Support system for the exodraft chimney fan Prior to installation of the chimney fan i...

Page 6: ...hroat of the fan the hole in the fiber mat should correspond to the throat Step 2 Preparation of fan y Locate the installation brackets in the grooves on the underside of the fan base using the bolts...

Page 7: ...that the bolts shall be installed from the bottom side in the two inner holes y Adjust the final position of the brackets ensuring that there is clearance between the brackets and the flue wall If the...

Page 8: ...e and bolted onto the top When installing multiple fans it is extremely important that the fans are of the same model and size and they must be controlled in tandem by one 1 motor speed control y A si...

Page 9: ...lation of Proven Draft Switch PDS y A safety system must be interlocked with the appliance s The safety system could utilize a Proven Draft Switch a thermal switch or a flow switch The device must be...

Page 10: ...same temperature rating Otherwise insulation may melt or degrade exposing bare wire 4 2 Wiring diagram for single fan with fan speed control The wiring diagram below shows the wiring of the chimney fa...

Page 11: ...ng must be in flexible or rigid metal conduit LEGEND 24 VAc 120 VAC WEATHERPROOF BOX N FAN SPEED CONTROL ORANGE RED WHITE BLACK GREEN FAN MOTOR WEATHERPROOF BOX ORANGE WEATHERPROOF BOX L 24V GAS VALVE...

Page 12: ...here in the system Check the system for flue gas spillage Mark this setting on the fan speed control cover 5 3 Adjusting the Proven Draft Switch setting y Remove the snap on cover from the conduit enc...

Page 13: ...housing unless power to the chimney fan has been disconnected 6 3 Chimney cleaning intervals It is extremely important to keep the chimney flue clean from products of combustion and deposits Soot can...

Page 14: ...eed control There is power to the fan but it hums and does not turn The motor run capacitor may be bad Creosote may stick Check capacitor and replace if necessary Clean fan The fan seems to work fine...

Page 15: ...Notes 15 3000270 RS gas and oil 20210818 international...

Page 16: ...www exodraft com Notes...