background image

2.2 Planning ahead

 

1.  Observe proper combustion air requirements.
2.  Provide a firm support system for the chimney fan.
3.  Determine the type of system involved.
4.  Observe proper safety measures are taken to assure safe use of the wood burning  appliances

Combustion air requirements: 

Provisions for combustion air must be in accordance with applicable local codes. 

If the heating system is installed in an unconfined space

, adequate air will be available via normal infiltration. 

If the heating system in installed in a confined space,

 (a space with a volume less than 50 cubic feet per

 

1,000 Btu/hr of input for all 

fuel burning equipment) or building construction is unusually tight, adequate air for

 

combustion must be provided by two openings: one 

located about 6” below the ceiling, the other about 6” above the

 

floor.  

Each opening must have a minimum free area as follows:

1.  One square inch per 4,000 Btu/hr of input when communicating directly with the outside or through a vertical duct.
2.  One square inch per 2,000 Btu/hr when communication through horizontal ducts to the outside. 
3.  One square inch per 1,000 Btu/hr when ventilation air is provided by openings in doors, etc. to adjoining spaces

 

having adequate 

infiltration.

 

CAUTION

Adequate fresh air must be provided for combustion; otherwise, improper operation and 

inadequate venting of deadly flue gases may result.

Support system for the exodraft chimney fan

Prior to installation of the chimney fan, it must be assured the chimney can

 

safely carry the weight of the chimney fan.

A steel chimney should be well supported at the roof penetration point.

 

If the chimney extends more than 20’ above

 

the roof, the 

chimney and the fan should be secured by wires attached on the chimney and on the roof at 2 to 3

 

different points.

Brick chimneys usually do not need any kind of support to carry the weight of the chimney fan.

System type 

Direct connect oil or gas appliances (no draft hood) normally do not require any mechanical draft adjustment.

 

However, if there are long 

horizontal breechings and far between the appliances, it is a good idea to install

 

mechanical vent dampers, so adjustments of the draft 

can be easily made.
Draft hood systems could generally speaking have vent dampers installed. The vent dampers are used to balance

 

the system and assure 

that only a minimum of dilution air is pulled through the draft hoods.

Safety devices 

Local codes usually require installation of safety devices, when mechanical draft is provided in an oil or gas fueled

 

system.

Make sure a differential pressure switch (proven draft switch) is installed to assure that no appliance will fire unless

  

there is a proven draft.

  

5

3000270  RS gas and oil 20210818 - international

Summary of Contents for RS 009

Page 1: ...ation Chapters 1 2 Mechanical installation Chapter 3 Electrical installation Chapter 4 Start up and configuration Chapter 5 Maintenance and troubleshooting Chapter 6 READ AND SAVE THESE INSTRUCTIONS R...

Page 2: ...g place 5 This unit must be grounded How to use this manual This installation manual does not contain any system design documentation System design documentation is available from exodraft Accessories...

Page 3: ...ney fan must be interlocked with the connected appliance s to insure proper combustions and to avoid flue gas spillage 1 2 Shipping The packing list attached to one of the packages clearly lists all i...

Page 4: ...4 422 478 C in 10 8 13 5 15 5 17 4 mm 275 344 395 441 D in 3 0 3 3 3 9 3 9 mm 75 85 100 100 E in 9 4 11 6 13 5 15 4 mm 238 294 342 391 Temperature Rating Interm 575 F 300 C Cont 482 F 250 C Capacity 1...

Page 5: ...st be provided for combustion otherwise improper operation and inadequate venting of deadly flue gases may result Support system for the exodraft chimney fan Prior to installation of the chimney fan i...

Page 6: ...hroat of the fan the hole in the fiber mat should correspond to the throat Step 2 Preparation of fan y Locate the installation brackets in the grooves on the underside of the fan base using the bolts...

Page 7: ...that the bolts shall be installed from the bottom side in the two inner holes y Adjust the final position of the brackets ensuring that there is clearance between the brackets and the flue wall If the...

Page 8: ...e and bolted onto the top When installing multiple fans it is extremely important that the fans are of the same model and size and they must be controlled in tandem by one 1 motor speed control y A si...

Page 9: ...lation of Proven Draft Switch PDS y A safety system must be interlocked with the appliance s The safety system could utilize a Proven Draft Switch a thermal switch or a flow switch The device must be...

Page 10: ...same temperature rating Otherwise insulation may melt or degrade exposing bare wire 4 2 Wiring diagram for single fan with fan speed control The wiring diagram below shows the wiring of the chimney fa...

Page 11: ...ng must be in flexible or rigid metal conduit LEGEND 24 VAc 120 VAC WEATHERPROOF BOX N FAN SPEED CONTROL ORANGE RED WHITE BLACK GREEN FAN MOTOR WEATHERPROOF BOX ORANGE WEATHERPROOF BOX L 24V GAS VALVE...

Page 12: ...here in the system Check the system for flue gas spillage Mark this setting on the fan speed control cover 5 3 Adjusting the Proven Draft Switch setting y Remove the snap on cover from the conduit enc...

Page 13: ...housing unless power to the chimney fan has been disconnected 6 3 Chimney cleaning intervals It is extremely important to keep the chimney flue clean from products of combustion and deposits Soot can...

Page 14: ...eed control There is power to the fan but it hums and does not turn The motor run capacitor may be bad Creosote may stick Check capacitor and replace if necessary Clean fan The fan seems to work fine...

Page 15: ...Notes 15 3000270 RS gas and oil 20210818 international...

Page 16: ...www exodraft com Notes...

Reviews: